Sommaire des Matières pour Johnson Controls VP140 Serie
Page 1
Istr. 240D VP140 1/2 Inch to 1-1/4 Inch (DN15-DN32) Pressure Independent Control Valve - Rotary Installation Instructions P/N 14-88360-03419, Rev. D Issued September 2020...
Caution Johnson Controls, Inc. does not accept any liability for improper or wrong use of this product. Proper water treatment is rec- ommended; refer to the VDI 2035 Guideline. Furthermore, maximum iron oxide in the water passing through control valve (PICV) should not exceed 25 mg/Kg (25 ppm).
Page 3
Instrucciones de cableado para el técnico • Todo el cableado cumple con los códigos locales y debe estar a cargo de personal autorizado únicamente. • Mantenga separado el cableado de alta y baja tensión. • Cuando use cables de trenzado múltiple, aplique una virola en el extremo del cable. •...
For additional installation information and technical specifications, refer to the appropriate document: • VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions Part No. 14-1336-15 • VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation Instructions Part No.
Page 8
Flow direction | Sens du débit | Dirección del flujo The following diagram illustrates the flow direction. Use this diagram as a guide on how to attach the actuator. If flow reversal is possible, mount a a non-return valve. See Table 10 for the minimum differential pressure required. Le diagramme ci-dessous illustre le sens du débit.
Measuring differential pressure | Mesure de la pression différentielle |Medición de la presión diferencial To ensure that the valve is working in the operating range, measure the differential gauge across the valve. The valve is in the operating range if the value at P1-P2 (ΔP) is higher than the start up value. If the ΔP measured value is lower than the start up value, then the valve works as a fixed orifice valve.
-10 to 120 °C Connection ½” FNPT Leakage Class IV IEC 60534-4 Compliance Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the PED (Pressure Equipment Directive) Table 10: VP140Mxx VP140MAG VP140MCC VP140MAU Flow rate max.
Page 13
Connections 1" FNPT Union Leakage Class IV IEC 60534-4 Compliance Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the PED (Pressure Equipment Directive) Table 12: VP140Pxx VP140PAY VP140PCD Flow rate max.