Before You Install

IMPORTANT CONSIDERATIONS WHEN INSTALLING THE STATION
The station must be installed by a certified electrician.
The station has built-in protection against overvoltage conditions
and leakage current to ground.
Any alteration to any part of the charging station will void the
warranty.
Connecting your new charging station requires:
- Single-Phase 120/240 VAC supply (figure 1) or
3-Phase 120/208 VAC supply (figure 2)
- A connection with 6 AWG to 8 AWG copper conductors
- Protection by a 40A double circuit breaker or two fuses
- 2 phases and a ground connection with 120 VAC between
each phase and ground
Note: Neutral is not required.
Maximum output power: 7.2 kW @ 240 V or 6.2 kW @ 208 V
Figure 1
Single-Phase 120/240 VAC
Figure 2
3-Phase 120/208 VAC
6
120
VAC
GND
120
VAC
Ground
A
GND
C
B
Ground
L1
240
VAC
L2
Ground
L1
Charging
208
Station
VAC
L2
September 2018 | flo.com | Installation guide | FLO Home X5
Charging
Station