Generalities; Direction Of Rotation; De-Aeration; Output Regulation - ITT A 402 Serie Instructions D'installation Et D'entretien

Circulateurs de chauffage
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

A_AD
16.05.2007
8:22 Uhr
58
Seite 58
english
6. Initiation/operating control

6.1 Generalities

Fill and de-aerate the system properly.
Only put the pump into operation when the system is full.
Switch on the distribution voltage.

6.2 Direction of rotation

Simple control of the direction of rotation with push button:
Compare the motor shaft's direction of rotation
with the direction of rotation indicated on the type plate.

6.3 De-aeration

The pump, and especially the engine compartment,
is automatically de-aerated after a brief operational period.
If a very quick de-aeration is desired, proceed as follows:
– Switch off the pump
– Lower the system pressure to 0.2 bar
– Loosen the screw plug (roughly one turn counter-clockwise)
until water comes out.
There is a danger of scalding
Depending on the temperature and the system pressure,
the hot pumped fluid may be emitted as a liquid or a gas.
– Never remove the screw plug completely
The pump may suck air in.
A great volume of fluid may be lost.
– Switch the pump on and off some 5 to 8 times
until only water comes out of the screw plug.
– Tighten the screw plug.
– Increase the system pressure
– Switch the pump on.

6.4 Output regulation

Fit correct cover on electronics
Warning
(with several pumps).
Refer to type designation in cover.
The desired flow rate is set using the turning knob
on the pump's electronics.
(infinite from e.g. 1 to max).
The pump can be set to the system's specific needs using
infinite adjustments.
(Flow volume V [m
3
/h])
Setting value:
– Specifications of heating planner
– Start with the first level.
If the heating elements removed do not become hot,
raise the settings to a higher level. Wait for a reaction.