Power limitation.
Minimum speed:
min 1, min 2
Power limitation
Analogue input
0..10 V /0.20 mA
When setting the speed
externally:
Comment:
If the analogue input
(SWITCH 4) is ON (71-72),
the turning knob
on the control system
(pressure adjustment)
does not have a function
any longer:
If the analogue input is ON
and the clamps 71 and 72
are not connected, the pump
runs at minimum output
(no voltage/current
= 0V/0mA).
Seite 56
english

5.3 Settings

The pump is supplied ex works with power limitation.
Further setting possibilities:
– min. 1 / min. 2 (minimum speed)
– Proportional pressure / constant pressure
– «Automatic» minimum speed
– Analogue input 0-10V / 0-20mA
SWITCH 1 to 5
Setting ex works