Technical Data
Input
Nominal voltage U
:
N
Voltage range:
at 10% residual ripple:
at 48% residual ripple:
Nominal consumption
BG 5929
AC 24 V:
DC 24 V:
BG 5929/100
AC 24 V:
DC 24 V:
Nominal frequency:
Control current:
BG 5929
AC 24 V:
DC 24 V:
BG 5929/100
AC 24 V:
DC 24 V:
Output
Contacts
BG 5929.60:
BG 5929.54:
BG 5929.04/100:
BG 5929.48/100:
The NO contacts are safety contacts.
The NC contacts 41-42 and 51-52 can only be used for monitoring
Operate time:
Release time:
Contact type:
Nominal output voltage:
Thermal current I
:
th
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
Electrical life
to 5 A, AC 230 V cos ϕ = 1:
Permissible switching
capacity:
Short circuit strength
max. fuse rating:
max. line circuit breaker:
Mechanical life:
General Data
Operating mode:
Temperature range
Operation:
Storage :
Altitude:
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
EMC
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
AC/DC 24 V
AC 0.8 ... 1.1 U
N
DC 0.9 ... 1.1 U
N
DC 0.8 ... 1.1 U
N
2.1 VA
1.5 W
2 x 1.1 VA
2 x 0.75 W
50 / 60 Hz
60 mA
65 mA
2 x 40 mA
2 x 40 mA
5 NO contacts,
1 NC contact for feedback circuit
4 NO contacts,
2 contacts for feedback and indicator
circuit
4 NO contacts
1 NC contact for feedback circuit
3 NO contacts
2 contacts for feedback and indicator
circuit
max. 20 ms
max. 35 ms
relay, forcibly guided
AC 250 V
max. 5 A
see total current limit curve
3 A / AC 230 V
IEC/EN 60 947-5-1
1 A / AC 230 V
IEC/EN 60 947-5-1
1 A / DC 24 V
IEC/EN 60 947-5-1
1 A / DC 24 V
IEC/EN 60 947-5-1
4 A / 24 V at 0.1 Hz
4 A / 24 V at 0.1 Hz
≥ 2 x 10
switching cycles
5
1200 switching cycles / h
IEC/EN 60 947-5-1
6 A gL
C 8 A
10 x 10
switching cycles
6
Continuous operation
- 25 ... + 55 °C
- 25 ... + 85 °C
< 2.000 m
4 kV / 2 (basis insulation) IEC 60 664-1
IEC/EN 62 061
Limit value class B
EN 55 011
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
Thermoplast with V0 behaviour
according to UL subject 94
Technical Data
Vibration resistance:
Frequency / Amplitude:
Acceleration:
Climate resistance:
Terminal designation:
Wire fixing:
Mounting:
Weight:
Dimensions
Width x heigth x depth:
UL-Data
The safety functions were not evaluated by UL. Listing is accomplished
according to requirements of Standard UL 508, "general use
applications"
Nominal voltage U
:
N
Ambient-temperature:
Switching capacity:
NO contact:
NC contact:
Wire connection:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
Standard Type
BG 5929.60 AC/DC 24 V 50/60 Hz
• Article number:
• Output:
• Nominal voltage U
:
N
• Width:
Variants
BG 5929._ _ /61:
with UL-approval
BG 5929._ _ /100:
for 2-channel connection,
with 2 LEDs
Ordering example for variants
BG5929 ._ _ /100
AC/DC 24 V
Troubleshooting
Failure
LED "K1/K2" does not light up
Maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
15
IEC/EN 60 068-2-6
10 ... 57 Hz, 0,075 mm constant
57 ... 150 Hz, 1 g constant
25 / 055 / 04
IEC/EN 60 068-1
EN 50 005
terminal screws M 3.5
box terminal with wire protection
DIN rail
IEC/EN 60 715
180 g
22.5 x 84 x 121 mm
AC/DC 24 V
-15...+50° C
Pilot duty B300
5A 250Vac G.P.
5A 24Vdc
5A 250Vac G.P.
5A 24Vdc
60°C / 75°C copper conductors only
AWG 20 - 12 Sol Torque 0.8 Nm
AWG 20 - 14 Str Torque 0.8 Nm
0050807
5 NO contacts, 1 NC contact for
feed back circuit
AC/DC 24 V
22.5 mm
50/60 Hz
Nominal frequency
Nominal voltage
Variant, if requested
Contacts
Type
Potential cause
Power supply not connected
BG 5929 / 25.09.18 en / 020A