Safety Technique
SAFEMASTER
Extension Module
BG 5929
Product Description
If more safety cicuits have to be switched, than a safety module provi-
des, the extension module BG 5929 is used. It offers safe and reliable
contact multiplication and re-enforcment for safety modules with moni-
toring of the feedback circuit. Safe semiconductor outputs can be exten-
ded by relay output contacts. The extension module has forcibly guided
contacts and can be delivered with different contact arrangements.
Circuit Diagrams
A1
Y1
Y2
(+)
13
23
33
43
A1
13 23 33 43
51
K1
K2
A2
14 24 34 44
52
14
24
34
44
A2
51
52
(-)
BG 5929.54
A1
A3
Y1
(+)
(+)
13
23
33
43
13 23 33 43 Y1
A1
K1
A2
A3
K2
14 24 34 44 Y2
A4
14
34
44
24
A2
A4
Y2
(-)
(-)
BG 5929.04/100
Connection Terminals
Terminal designation
A1 (+), A3 (+)
A2 (-), A4 (-)
13, 14, 23, 24, 33, 34,
43, 44, 53, 54
41, 42, 51, 52
Y1,Y2
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
A1
Y1
Y2
(+)
13
23
33
43
Y1
A1
13 23 33 43 53 Y1
K1
K2
Y2
A2
14 24 34 44 54 Y2
14
24
34
44
A2
53
54
(-)
BG 5929.60
A1
A3
Y1
(+)
(+)
13
23
33
41
13 23 33
A1
K1
A2
A3
K2
14 24 34
A4
14
34
24
42
A2
A4
Y2
(-)
(-)
BG 5929.48/100
Signal description
+ / L
- / N
Forcibly guided NO contacts for
release circuit
Forcibly guided indicator output
Forcibly guided feedback circuit
Your Advantages
• Safety contact multiplication
Features
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
when connected to a suitable safety module
• Redundant and forcibly guided contacts
• Output: max. 5 NO contacts or 4 NO contacts / 1 NC contact
• 1- or 2-channel connection
• LED indication for operation
• Removeable terminal strips
• Width 22.5 mm
Approvals and Markings
* see variants
Applications
Contact multiplication of emergency-stop modules and safety door monitors.
Indication
BG 5929
LED K1/K2:
BG 5929/100 LED K1:
LED K2:
41
Y1
42
Y2
13
*
Canada / USA
on, when operating voltage applied
on, when relay K1 energized
on, when relay K2 energized
BG 5929 / 25.09.18 en / 020A