Electrical Connections - CIAT YUNA II Serie Manuel D'instructions

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
 
  
!LL lELD ELECTRICAL CONNECTIONS ARE THE RESPONSIBILITY OF
the installer.
Please refer to the hydronic module manual.
WARNING: Make refrigerant connections before

electrical connections.

Make ground connection prior to any other electrical
connections.
Size
50
Maximum running
A
12 A
current
Nominal
single-phase
50 Hz
230 V
voltage
Operating voltage
50 Hz
min 198V ÷ max 264V
limits
Also check the supply voltage and frequency of the indoor
unit.
Only for the 3Ph power supplied units this equipment
complies with IEC 61000-3-12 provided that the short
circuit power Ssc is greater than or equal to 1,32 MVA at
the interface point between the user's supply and the
public system. It is the responsibility of the installer or user
of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the
equipment is connected only to a supply with a short-
circuit power Ssc greater than or equal to 1,32 MV.
Remove the front panel, the electric parts appear at the
front side.
The power supply cables can be inserted into the pipe
holes. Enlarge the pipe holes if they are too small. Be sure
TO lX THE POWER CABLE AND INDOOROUTDOOR CONNECTING
cable with bundling band sold on the market so that they
do not make contact with the compressor and the hot
pipes. To ensure good tensile strength, the electric cables
must be fastened using the cable-holder on the plate (See
lG  
12
65
90
115
120
150
12 A
23 A
23 A
15.4 A
15.4 A
400 V
min 376V -
max 424V
IMPORTANT (1Ph units):
The ground wire for the indoor unit outdoor
unit connection cable must be clamped to a
soft copper tin-plated eyelet terminal with M4
screw hole.
WARNING: For the 3Ph units be sure to attach the
PROVIDED CLAMP lLTER AND THE SUPPLIED STRAIN RELIEF TO THE
power supply wire in order to conform to safety and EMC
STANDARD 3EE lG 
#ONNECTION TO UNITS 95.! )) INDOOR 0H SEE lG 
Cable type and size (\-]): H07RN-F 4x1 mm
Cable type and size ([): H07RN-F 3x2,5 mm
#ONNECTION TO UNITS 95.! )) INDOOR 0H SEE lG 
Cable type and size (\-]): H07RN-F 3x1 mm
Cable type and size ([): H07RN-F 5x2,5 mm
Indoor
Size the cable, the cables must be H07
- outdoor
RN-F type.
Connect the connecting cable to the
TERMINAL AS IDENTIl ED WITH THEIR
respective numbers on the terminal
block of indoor and outdoor unit.
Power supply
Size the cable, the cables must be H07
RN-F type.
According to the installation
instructions, all devices for disconnection
from the power supply mains must have
a contact opening (4 mm) to allow total
disconnection according to the
conditions provided for the overvoltage
class III.
To prevent any risk, the power cable
must only be replaced by the technicians
of the after-sales service (type Y
attachment).
2
2
2
2

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières