7. Specification
7.1 Specification
Table7. Electrical Specification
Model
Capacity
Watt
Input voltage range
Input
Frequency range
Voltage
Voltage Regulation
(Batt. Mode)
Output
Frequency
Waveform
Line Mode
Overload
rating
Battery Mode
Battery Type
Internal
Backup Time
battery
(at full load)
Recharge Time
(EBM) External
battery module
Battery Type
(optional)
RS-232 port
Dry-Contact-output
AS/400 Card
Interface
USB
SNMP Card
EPO port
1000
1500
1000E
1000S
1500S
900W
900W
1350W
161-276VAC
50/60Hz ±5Hz for Normal Mode
40-70Hz for Generator Mode
220/230/240VAC
±5%
50Hz or 60Hz
Pure sinewave
110% -0%, +8%: shutdown after 3 minutes.
150% -0%, +10%: shutdown after about 200ms
110% ± 6%; shutdown after 30 seconds.
120 % ± 6 %; Shutdown after about 100ms
3 x
2 x
3 x
12V/7AH
12V/9AH
12V/9AH
4'30"
3'
3'
3 hours to
8 hours to
4 hours to
90% after
90% after
90% after
discharged
discharged
discharged
6 x
6 x
N/A
12V/7AH
12V/7AH
Yes
Yes(Not available for 1kVA E-model)
Optional(Not available for 1kVA E-model)
Yes
Optional(Not available for 1kVA E-model)
Yes(Not available for 1kVA E-model)
EN
2000
3000
2000S
3000S
1800W
2700W
6 x
6 x
12V/7AH
12V/9AH
4'30"
3'
3 hours to
4 hours to
90% after
90% after
discharged
discharged
12 x
12 x
12V/7AH
12V/7AH