UPS Status Display String Description:
The following table shows the description of the LCD display string:
Table4. UPS Status Display String
LCD Display String
STbY
IPVL
IPVH
IPFL
IPFH
NORM
AVR
bATT
TEST
OPVH
OPVL
OPST
OVLD
bATH
bATL
OVTP
FNLK
bTWK
User Setting String Description:
The following table shows the options that can be changed by user.
Table5. User Setting String
OPV
Output voltage mode select
AVR
Input type select
External
battery
EbM
(EBM)
TEST
Auto self-test
AR
Automatic restart
GF
Green function
bZ
Buzzer control
LS1
Load segment 1
LS2
Load segment 2
Description
UPS work at Standby mode
Input voltage is too low
Input voltage is too high
Input frequency is too low
Input frequency is too high
UPS work at Line mode
UPS work at AVR mode
UPS work at Battery mode
UPS work at battery life/function test mode
Battery mode, the output is too high
Battery mode, the output is too low
Output short
Overload
Battery voltage is too high
Battery voltage is too low
Internal temperature is too high
Fan is locked
Batteries are weak
[220]= 220V
[230]= 230V
[240]= 240V
[000]= Normal range mode
[001]= Wide range mode
[002]= Generator mode
module
0~9 is the number of external battery
module
[000]=Disable
[000]=Disable
[000]=Disable
[000]=Disable
[000]=Turn off
[000]=Turn off
EN
[001]=Enable
[001]=Enable
[001]=Enable
[001]=Enable
[001]=Turn on
[001]=Turn on