Mounting (Tower)

Mount all UPS models in an upright, tower position using included hardware. The user must
determine the fitness of hardware and procedures before mounting.
All UPS Models
Stand your UPS on its side with the LED/Control
panel at the top. Attach one rack mounting ear
to each side of the UPS using included
A
screws
. Attach the rack mounting ears to the
B
floor with user-supplied hardware.

Quick Installation

Plug the UPS into an outlet on
1
a dedicated circuit.*
NOTE! after you plug the UPS into a live
AC outlet, the UPS (in "Standby" mode)
will automatically charge its batteries,
but will not supply power to its outlets
until it is turned ON (see Step 3 below).
Note: UPS system will function properly upon
initial startup; however, maximum runtime for the
unit's battery will only be accessible after it has
been charged for 24 hours.
Plug your equipment into the
2
UPS.*
* Your UPS is designed to support only electronic
equipment. You will overload the UPS if the total
VA ratings for all the equipment you connect
exceeds the UPS's Output Capacity. To find your
equipment's VA ratings, look on their
nameplates. If the equipment is listed in amps,
multiply the number of amps by 120 to
determine VA. (Example: 1 amp × 120 = 120
VA). If you are unsure if you have overloaded the
UPS's outlets, see "OUTPUT LOAD LEVEL " LED
description.
Turn the UPS ON.
3
Press and hold the "ON/OFF/STANDBY"
button for one second. The alarm will beep
once briefly after one second has passed.
Release the button.
13-12-130-93328A.indb 5
B
A
1
SMART1000RM1U
Shown
2
3
5
B
A
NEMA 5-15P
Plug Shown
1/6/2014 2:59:21 PM