Resistance measured on sensors
Position/Ceiling
Interrupted
Interrupted
• About 5.700 ohm at 20°C
• About 4.700 ohm at 25°C
Sensor short-circuit
Short-circuit of both sensors
REFERENCE TABLE FOR SENSOR TEMPERATURE/RESISTANCE
Reference temperature in °C
TROUBLESHOOTING VORT DELTA T
Position/Floor
Interrupted
• About 5.700 ohm at 20°C
• About 4.700 ohm at 25°C
Interrupted
(NTC 4.7K at 25°C)
-10
-5
0
5
10
15
20
25
30
35
40
45
Jumper: position 1
Fan status
Idle
Idle
Rotation at maximum
speed
Rotation at maximum
speed
Rotation at maximum
speed
Reference resistance in Ohm
25217
19392
15040
11743
9241
7330
5855
4700
3777
3071
2512
2066
Jumper: position 2
Rotation at minimum
speed
Rotation at minimum
speed
Rotation at maximum
speed
Rotation at maximum
speed
Rotation at maximum
speed
13