Endress+Hauser
®
ReadWin
2000 interactive menu operation
Presettable parameters
Expanded settings
• Cold junction compensation (internal/external on TC con-
nection)
• Temperature external (on TC with cold junction compensa-
• Compensation resistance (0 to 30 Ω) on 2-wire connection
tion external)
• Fault condition reaction (
• Output (4 to 20 mA / 20 to 4 mA)
• Filter (0 to 60 s)
• Offset (-9.9 to +9.9 K / -18 to +18 °F)
• TAG (Measurement point description)
• Identifier (Descriptor)
Service functions
• Simulation (on/off)
• Reset/factory default (=Reset 182)
• Operation code (=release code 281)
Note!
• Standard model: > 21.5 mA
* Guaranteed values for setting "high alarm" (≥ 21 mA):
• Advanced diagnostic model (> SW 1.05.01): ≥ 22.5 mA
®
For detailed ReadWin
2000 operating instructions please read the online
documentation contained in the ReadWin
≤
≥
3.6 mA or
21.0 mA)*
®
2000 software.
TMT182
17