Pin connection for pluggable sensors
Pin connection for pluggable sensors (front view)
4
3
4
1
2
1
Electrical connection
Series 30 (NAMUR)
• Protective earth-terminal for sensors with metal version and Ex protection
• For inductive loads, a corresponding protective circuit (e.g. freewheeling diode) must be provided.
Adjustment of sensitivity
Sealing screw (A)
Maintenance, repair, disposal
• Maintenance for this device is not necessary when used as intended.
• It is not possible to repair the device. If you have any problems, please contact directly your customer
service.
• Please dispose of the device in a way that is environmentally friendly according to the national
regulations.
10
*
3
Protective earth-terminal for sensors with metal version
and with Ex protection. After mounting, the plug-and-socket
connector has to be protected by means of the protective clip
*5
enclosed with the sensor.
2
Series 40 (NAMUR)
Potentiometer (B)
Series 40 analogue
For adjustable sensors the potentiometer is placed under
a sealing screw (A). For some plug-in sensors and sensors
with special housing (B) the potentiometer is placed on
the side without a cover.
Adjustment:
• Turn clockwise to increase sensitivity
• Turn anti-clockwise to decrease sensitivity
KAS non-flush mountable for level control:
• Immerse the active area (= thread-free zone or 25 mm)
into the medium.
• Turn the potentiometer clockwise until the sensor
switches.
• Then turn the potentiometer a further 90° to the right
(= reliable switching).
• If the sensor switches immediately when immersing
the sensor then turn the potentiometer to the left to the
switching point and then to the right again as described
above.