nVent RAYCHEM NGC-20-C-E Guide D'installation, D'utilisation Et De Maintenance page 8

Masquer les pouces Voir aussi pour NGC-20-C-E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 39
Temperature sensors
Type
Home
EN
Quantity
DE
FR
PT
Communications
RU
Physical network
Protocol / topology
Cable and maximum length
Maximum quantity of controllers in
one network
(ModBus) Network address
Programming and setting
Method
Units of measure
Memory
LED indicators
NGC-20-C-E
NGC-20-CL-E
Measuring ranges
Temperature range controller
Temperature range limiter
Voltage
Load Current
Ground fault current
Heater Time Alarm
Relay Cycle Alarm
Ordering information
nVent RAYCHEM NGC-20 control units
Product name
Part number & (weight)
Product name
Part number & (weight)
|
8
nVent.com/RAYCHEM
100 Ω platinum, 3-wire, α = 0.00385 Ω/°C. Can be extended with a three core shielded or
braided cable of maximum 20 Ω lead resistance per conductor.
Two RTD inputs for the controller plus one independent temperature input for the limiter. In
case it is required, more RTDs can be monitored with optional RMM2 units. All temperature
sensors are permanently monitored for "sensor open" and "sensor break"
RS-485 and Class 1 Bluetooth
ModBus RTU or ASCII. Multi drop / Daisy chain
Shielded twisted pair cable, 0.5 mm² (AWG 24) or larger. Maximum cable length between
should be no more than 1200 m.
Max. of 247 units per NGC-UIT or per communication port
Software programmable via nVent RAYCHEM NGC-CMA-NH or nVent RAYCHEM
NGC-CMA-EX
Through handheld programming device nVent RAYCHEM NGC-CMA2 and a wireless
Bluetooth connection or via RS485 interface and nVent RAYCHEM Supervisor software or
nVent RAYCHEM User Interface Terminal (NGC-UIT-ORD, NGC-UIT-OUT) and customized
nVent RAYCHEM software.
°C or °F, software selectable.
Nonvolatile. There is no loss of parameters after the event of power outage or long term
shut down. Data holding time ~10 years.
Status LEDS are available for:
Heater, Alarm, RS485 communication, Bluetooth communication
Heater, Alarm, Limiter (tripped), RS485 communication and Bluetooth.
From –200°C to +700°C in steps of 1K
From –60°C to +599°C in steps of 1K (NGC-20-CL-E only)
From 50 VAC to 305 VAC
From 0.3 A to 30 A
From 10 mA to 250 mA
From 1 to 1x 106 hours
From 0 to 2x 106 operations
NGC-20-C-E (Standard temperature control unit)
1244-007035
(3.3 kg.)
NGC-20-CL-E (Temperature control unit with integrated temperature limiter)
1244-007036
(3.4 kg.)
RAYCHEM-OM-INSTALL130-NGC20CLE-ML-2204

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ngc-20-cl-e

Table des Matières