CAUTION: Install certainly the decorative panel.
Cool air leakage causes sweating.
Good example
Fit the insulator (this part) and
be careful for cool air leakage
Indoor Unit Drain Piping
[Floor Standing Type]
1. The drain hose should point downward for
optimum drainage.
2. Incorrect Installation Examples:
Do not raise
Water
leakage
How to use the finishing tape for the drainpipe
After applying the glue, insert
the drainpipe completely.
Connecting pipe
Glue
Air conditioner
unit
Ceiling
board
Decorative panel
Accumulated
drain water
Air
Water
Kinking
leakage
Wind the insulating material
to connect the insulating
material of the indoor unit and
the insulating material of the
connecting pipe.
Refrigerant pipe
Drain pipe
Water drops fall.
Bad example
Tip of drain hose
dipped in water
Water
leakage
Ditch
Wind the finishing tape
around the connecting pipe,
the drainpipe, and the wire.
Connecting wire
Refrigerant pipe
(Indoor unit}
Insulating material
Indoor Unit Drain Piping
Air conditioner unit
Air
Cool air leakage
(no good)
Ceiling
board
Decorative
panel
Downward slope
Less than 50mm
(1 31/32 inch) gap
Pipe
Flexible drain hose
Pipe
Finishing tape
Installation Manual 25