Modbus Memory Map - S&P CTB ECOWATT Instructions De Montage Et D'utilisation

Masquer les pouces Voir aussi pour CTB ECOWATT:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

MODBUS message
Direction
Function
8 bits
8 bits
Format for each byte in RTU mode is:
• System codes: 8–bit binary
• Bits per Byte: 1 bit to START (start)
8 bits for data, the most signifi cant bit is sent fi rst
1 bit for parity (Even parity is required)
1 bit for STOP (end)

8.2. MODBUS MEMORY MAP

Holding registers
N°REG.
Register
0
TipoMotor
1
ModoFun
2
SensorPI
3
Sensor1
4
Sensor2
5
PIRange
6
SetPoint
7
Kp
8
Ki
Dates
CRC verifi cation
N x 8bits
16 bits
Min.
Max.
Description
0
1
0=PI_Presión
1=PI_Caudal
2=Proporcional
3=Max-Min
0
7
4=PI_Presión+RTC
5=PI_Caudal+RTC
6=Proporcional+RTC
7=Max-Min+RTC
0=Interno
1=IN1 0-10V
0
4
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
0
7
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
7=NTC 100K
1=0-10V %HR
2=4-20mA %HR
0
6
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
50
1250
SensorPI=0
50
2500
SensorPI<>0
100
9900
Sensor<>0
0=Interno
1=IN1 0-10V
2=IN1 4-20mA
0
5
3=IN2 0-10V
4=IN2 4-20mA
5=ConsolaMODBUS
(PROSYS ECOWATT)
1
250
Increases 1
1
250
Increases 1
Default
0=AC
1
1=DC
0
0
0=NO
0
0=NO
0
400Pa
5
20
20
57
Comments
Motor type
Operation mode
Sensor type in PI
PRESSURE or PI VOLUME
mode
Sensor type in
PROPORTIONAL mode
and analog input signal 1
Sensor type in
PROPORTIONAL mode
and analog input signal 2
Range sensor in PI
PRESSURE mode
Set point in PI PRESSURE
mode
Proportional constant in PI
PRESSURE mode
Integral constant in PI
PRESSURE mode

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Crhb ecowattCrvb ecowatt

Table des Matières