The lamp does not react
to a press of the button
as expected.
Possible cause:
If you cannot rectify the fault, please perform a RESET of the lamp (see corresponding chapter
in these operating instructions) or contact the customer service of your lamp manufacturer.
Ask your lamp manufacturer about the operating mode to be set for your lamp.

Technical Data

Device name:
Supply connection:
load connection:
Control connections:
Button input:
Sensor connection:
Operating voltage:
Protection:
Power consumption:
Ambient temperature:
Settable light value:
Degree of protection:
Class of protection:
Ce requirement:
Dimensions:
Signal of the leD:
The conformity with the relevant EU directives
is confirmed by the CE-Symbol.
The button is been pressed for too long.
Please note: Press the button to alter the brightness until the lamp
has the desired brightness. For all other functions, only press the
button briefly.
DIM MULTI 3
L, N, PE (PE not required)
L', switched output, max. 5 A ohmic load or 10 OSRAM electronic
ballast 1-lamp or 5 OSRAM electronic ballast 2-lamp or 5 OSRAM
electronic ballast 3-/4-lamp
1...10 V control signal according to EN 60929 Annex E 2,
maximum 32 electronic ballast can be connected
Potential-free make contact, maximum line length 100 m
Maximum 4 sensors, maximum line length 100 m
230 – 240 V AC 50/60 Hz (no DC operation)
external 16 A
approx. 1.5 W
0C - + 50 C
20 –1000 Lux (measured at the sensor)
IP 20
II
EMC fulfilled according to EN 61547, low voltage according to
EN 60928
189 x 30 x 21mm (L x W x H),
Hole pitch for fastening: 180 mm
Presence detection: LED flashes on
Mode selection:
LED flashes according to table on page 14