Mounting the product

 Verify that the permissible ambient temperature is not exceeded.
 Verify that the product is not mounted the product on top of or next to a
non-insulated boiler part, above opening dampers at furnaces or to the
flue gas pipe.
 Verify that the float housing points vertically to the top.
1. Mount the product to the sheet metal boiler wall using the enclosed tap-
ping screws.
2. Use the bracket as a template when drilling the holes (Ø 3 mm).
 Verify that suitable oil hoses (as per DIN 4798-1) for connection to the oil
pump are used.
Mounting
 Verify that an oil filter is installed in
3. Connect the burner hoses to the
A
The connection to the filter "connec-
B
tion T" (b) can be made with the
optional, enclosed hose G
C
a G
D
the supply line upstream of the
product.
two threaded sockets R and V (A).
- The tightening torque is
25 ±5 Nm.
3
(D) union nut.
/
8
Flow-Control
EN
1
(C) and
/
4
15