ADJUSTMENTS, TO AVOID FLAME - DETACHMENT,
1) CORRECT POSITIONING OF THE ELECTRODES
2) NOZZLE: ATOMIZING ANGLE
Choose 60° nozzle
3) COMBUSTION-HEAD SETTING
Regulate the combustion-head one set-point further ahead than indicated in the instructions.
Example: the instructions require to set the combustion-head on set-point 3.5.
Instead, the setting is made on set-point 4.5.
4) FAN - AIR DAMPER ADJUSTMENT
Adjust the air damper of the fan, such as to obtain a smoke-number not inferior to 1.
(i.e. a combustion with the lowest possible excess-air).
2354
AT BURNER - IGNITION
4 ±
0.3 mm
D5288
A
MOVE THE ELECTRODE
HOLDER BACKWARDS TO
THE END
9
GB
6.5 ±
0.5 mm