Connection In The Terminal Compartment; Single Chamber Housing - KROHNE OPTIBAR PM 5060 C Notice Technique

Masquer les pouces Voir aussi pour OPTIBAR PM 5060 C:
Table des Matières

Publicité

OPTIBAR PM 5060 C

4.3.1 Connection in the terminal compartment

Procedure
• Unscrew the housing cover.
• If present, remove the display and adjustment module by turning it to the left.
• Loosen union nut of the cable gland.
• For preparation of connection cable se référer à
• Push the cable through the cable gland into the terminal compartment.
• Insert the wire ends into the open terminal connection according to the wiring plan. Flexible
cores with wire end sleeves as well as solid cores can be inserted directly into the terminal
openings. In case of flexible cores, press the spring terminal with a small screwdriver to open
the terminal opening.
• Check the proper hold of the wires in the terminals by lightly pulling on them.
• Connect the cable shield to the internal ground terminal, connect the outer ground terminal to
the customer/plant equipotential bonding.
• Tighten the union nut of the cable gland. The sealing ring must completely enclose the cable.
• Screw the housing cover back on.

4.3.2 Single chamber housing

Les appareils utilisés en atmosphère explosive sont soumis à des spécifications de sécurité
supplémentaires ; consulter à ce sujet la documentation Ex.
The following illustration applies to both the non-Ex as well as the the Ex ia, and the Ex d version.
Boîtier électronique
1 Alimentation / sortie signal
2 Adaptateur d'interface pour le module d'affichage et de réglage
3 Interface numérique
4 Borne de mise à la terre pour le raccordement du blindage du câble
01/2021 - 4004819902 - TD OPTIBAR PM 5060 C R02 fr
RACCORDEMENT ÉLECTRIQUE
Confection du câble
www.krohne.com
4
à la page 49.
53

Publicité

Table des Matières
loading

Table des Matières