2. Check the power supply to the unit.
The compressor does not work, the Triangle is constantly red:
The compressor has stopped automatically caused by a too high temperature on the condenser. If the unit does not
start again after 45 minutes, check the following:
3. Check that the fan(s) is running.
4. Check if the filter in the duct kit is dirty
5. Check if the condenser coil is dirty
6. Check if the room temperature is higher than 36ºC. If the room temperature is higher than 36°C, the unit
must be stopped.
7. Check that the duct openings are not covered.
The dehumidifier does not work and the Lighting on the display is green:
8. Check the built-in or the external hygrostat, if any, by setting it to a low relative humidity, e.g. 10 –
20%RH. If the unit still does not start, check the built-in or external hygrostat for defects.
If you cannot find the reason for the fault, switch off the unit immediately in order to prevent further damage.
Contact a service technician or a Dantherm representative.
NOTE!
If the dehumidifier is not functioning correctly, shut
it down immediately.
Disposal
This unit contains refrigerant type R407C and compressor oil. When scrapping the unit, bring the compressor to a
place of discharge, which is approved by the authorities.
16