Approvals, door dimensions, wall types
Approvals
These instructions form part of the following approvals for fire protection barriers.
NovoPorta
Fire protection
Premio
Approval no.
T30-1
Z-6.20-2205
GB
T30-2
Z-6.20-2205
T30-1 XTR Z-6.20-2326
T30-2 XTR Z-6.20-2326
T90-1
Z-6.20-2221
T90-2
Z-6.20-2221
MZ-1
–
MZ-2
–
E-S-1
–
E-S-2
–
Door dimensions and weights, wall types and thicknesses (in mm)
NovoPorta
Coordinating
Premio
size
min./max.
from 500 x 700
T30-1
to
1000 x 1750
Wall vent
from 625 x 1750
T30-1
to
1375 x 2500
Door
from 1375 x 1750
T30-2
to
2500 x 2500
from 625 x 1750
T30-1 XTR
to
1375 x 2500
Door
from 1375 x 1750
T30-2 XTR
to
2500 x 2500
from 500 x 700
T90-1
to
1000 x 1750
Wall vent
from 625 x 1750
T90-1
to
1375 x 2500
Door
from 1375 x 1750
T90-2
to
2500 x 2500
from 500 x 1500
MZ-1
to
1375 x 2500
from 1050 x 1500
MZ-2
to
2500 x 2500
from 625 x 1750
E-S-1
to
1375 x 2500
from 1375 x 1750
E-S-2
to
2500 x 2500
* Recommended wall thicknesses. Where measurements deviate from these values, the structural analysis and stability of the wall must be proven.
** Porous concrete wall using the version using adhesive
Other dry partition walls F60-A / F60-B and F90-A / F90-B according to general building code test certificates (see Approval)
20
Smoke protection
Sound insulation
DIN 18095
ISO 140 / 717
Z-6.20-2205
13-001982
Z-6.20-2205
14-001620
Z-6.20-2326
13-001982
Z-6.20-2326
14-001620
Z-6.20-2221
13-001982
Z-6.20-2221
14-001620
P-5009DMT DO
13-001982
P-5009DMT DO
14-001620
P-5009DMT DO
13-001982
P-5009DMT DO
14-001620
Clear passage
Max.
Masonry
width
door leaf
min./max.
weight
Conforming
to DIN 1053-1
min. com-
pressive
strength 12
from 416 x 616
–
> 115
to
916 x 1666
from 541 x 1708
250 kg
> 115
to
1291 x 2458
from 1291 x 1708
250 kg
> 115
to
2416 x 2458
from 541 x 1708
254 kg
> 115
to
1291 x 2458
from 1291 x 1708
254 kg
> 115
to
2416 x 2458
from 416 x 616
–
> 175
to
916 x 1666
from 541 x 1708
254 kg
> 175
to
1291 x 2458
from 1291 x 1708
254 kg
> 175
to
2416 x 2458
from 416 x 1458
250 kg
> 115 *
to
1291 x 2458
from 966 x 1458
250 kg
> 115 *
to
2416 x 2458
from 541 x 1708
250 kg
> 115
to
1291 x 2458
from 1291 x 1708
250 kg
> 115
to
2416 x 2458
Please keep these assembly, operating and maintenance instructions as long as you use the product!
RC2 Burglar resistance
DIN EN 1627
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
261 3200-GS S01
Concrete
F60-A /
F60-B /
F90-A
F90-B
dry partition
dry partition
walls
walls
Conforming
F60 not
to DIN 1045
approved
compressive
for T90
strength C12 / 15
> 100
> 100
> 130
> 100
> 100
> 130
> 100
> 100
> 130
> 120
> 100
–
> 120
> 100
–
> 140
> 100
–
> 140
> 100
–
> 140
> 100
–
> 100 *
> 100 *
> 130 *
> 100 *
> 100 *
> 130 *
> 100
> 100
> 130
> 100
> 100
> 130
RC3 Burglar resistance
DIN EN 1627
–
–
45-66/15
45-66/15
45-66/15
45-66/15
–
–
45-66/15
45-66/15
Porous
Reinforced
concrete
porous
shaped or
concrete
block bricks
pieces
Conforming
Approved for
to DIN 4165
general con-
compressive
struction,
strength 4
compressive
strength 4, laid
horizontally or
vertically
> 150
> 150
> 150
> 150
> 150
> 150
> 240
> 240
> 240
> 240
> 175
> 175
> 175
> 175
> 175
> 175
> 150 *
> 150 *
> 150 *
> 150 *
> 175 **
> 150 **
> 175 **
> 150 **