Timers and Delays Control Panel Alarm Messages
Water Sensing Timer
One minute timer to allow water from the pool to reach the Heat Pump before acquiring temperature. This timer
initiates when water first begins to run from stopped or low water flow conditions or when the heat pump is turned
ON. Countdown time is in Minutes and Seconds.
Restart Delay Timer
Five minute timer is a protection feature for the heat pump's compressor. This extends the life of the compressor's by
not allowing it to cycle on and off (i.e. adjusting set point up and down around actual temperature). Countdown time
is in minutes and seconds.
Defrost Delay Timer
Fifteen minute timer where the heat pump is in Defrost operation. Countdown time is in minutes and seconds. Refer
to page 18 for more details on the defrost cycle.
Pump Start Delay
One to Four Hour timer used in conjunction with the AutoSet feature. Counts down the time until the control board
will energize the internal contactor in the heat pump to turn on. Countdown time is in hours and minutes. See AutoSet
section for more details.
Heat Pump Runtime Timer
This feature is an adjustable timer to allow the heat pump to run (Green LED ON) and then turn OFF (Green LED OFF)
for a predetermined amount of time. During the selected time frame the Green LED Indicator is ON and the heat
pump will function in the normal mode of operation and/or the operator can change set points, functions, etc. The
heat pump's Green LED Indicator will turn OFF and the heat pump will stay OFF when time expires.
NOTE: It is possible to override Delay Times (for example to speed up servicing) by pushing the POOL/SPA and down
Arrow simultaneously