Campbell Hausfeld VT6195 Instructions D'utilisation page 10

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION INSTRUCTIONS (CONTINUED)
Installing A Shut-Off Valve
Figure 4 - Shut-off Valve
Apply air pressure to the piping installation and make sure all joints are free from leaks BEFORE
underground lines are covered. Before putting the compressor into service, find and repair all leaks in the
piping, fittings and connections.
Wiring
national codes.
Wiring must be installed in accordance with National Electrical Code and local codes and standards that
have been set up covering electrical apparatus and wiring. These should be consulted and local ordinances
observed. Be certain that adequate wire sizes are used, and that:
1.
Service is of adequate ampere rating.
2.
The supply line has the same electrical characteristics (voltage, cycles and phase) as the motor. Refer to
motor name plate for electrical ratings and specifications.
3.
The line wire is the proper size and that no other equipment is operated from the same line. The chart
gives minimum recommended wire sizes for compressor installations.
Make sure voltage is correct with the motor wiring.
NOTE: If using 208 volts single phase, make sure the motor name plate states it is rated for 208 volts single
phase. 230 volt single phase motors do not work on 208 volts unless they have the 208 volt rating.
Recommended wire sizes may be larger than the minimum set up by local ordinances. If so, the larger size
wire should be used to prevent excessive line voltage drop. The additional wire cost is very small compared
with the cost of repairing or replacing a motor electrically "starved" by the use of supply wires which are too
small.
A shut-off valve should be installed on the discharge port of the tank to control
the air flow out of the tank. The valve should be located between the tank and
the piping system.
Never use reducers in discharge piping.
When creating a permanently installed system to distribute compressed air,
find the total length of the system and select pipe size from the chart on
page 7. Bury underground lines below the frost line and avoid pockets where
condensation can gather and freeze.
All wiring and electrical connections must be performed by a qualified electrician
familiar with induction motor controls. Installations must be in accordance with local and
Overheating, short circuiting and fire damage will result from inadequate wiring.
Minimum Wire Size (Use 75°C Copper Wire)
HP
1-4 HP
5.0
Never install a shut-off valve between the compressor pump and
the tank. Personal injury and/or equipment damage may occur.
Amps
up to 22.0
8
Single Phase
230V
10 AWG
8 AWG

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vt6395

Table des Matières