Minimum clearance to combustible construction from appliance and vent surfaces:
Combustible Framing:
EN
-
-
-
Combustible Finishing:
-
-
Top Exit
-
-
Rear Exit
-
-
* HORIZONTAL VENT SECTIONS: A minimum of 1" (25mm) at the bottom and sides and 3" (76mm) at
the top of the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-1774
(supplied).
NOTE: The minimum clearances from the top of the horizontal vent pipe to combustible materials may
be reduced from 3" (76mm) to 1" (25mm) in those installations with a minimum 38" (965mm) vertical
vent rise made immediately off the fi replace collar.
* VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use fi restop spacer W500-0096 (not supplied).
42 9/16"
1081mm
W415-1616 / A / 04.15.16
0" to stand-offs
1" (25mm) to bottom and sides of the vent pipe*
3" (76mm) to top of the vent pipe*
0" to rear
0" to front face top and sides
50 1/2" (1283mm) to combustible enclosure top from base of the appliance
54" (1372mm) to ceiling from base of the appliance
36" (914mm) to combustible enclosure top from base of the appliance
54" (1372mm) to ceiling from base of the appliance
OUTSIDE
CHASE
18 9/16"
471mm
46 1/2" 1181mm
INSIDE
CHASE
46 1/2" 1181mm
SIDE
WALL
2" 51mm
18 9/16"
471mm