Télécharger Imprimer la page

Eaton PowerXL DG1VFD Serie Notice D'installation page 13

Masquer les pouces Voir aussi pour PowerXL DG1VFD Serie:

Publicité

PowerXL DG1 Series VFD
International Cable and Fuse Sizes—208 Vac to 240 Vac Ratings
208V Input
Frame
Amp
Current
Size
Suffix
(CT/I
)
H
FR1
3D7
3.2
4D8
4.4
6D6
6.1
7D8
7.2
011
10.2
FR2
012
10.2
017
16.2
025
23.1
FR3
031
28.7
048
44.4
FR4
061
56.4
075
69.4
088
81.4
FR5
114
105.5
143
132.3
170
157.3
FR6
211
195.2
261
241.4
1
Line and motor cable size is selected according to IEC 60364–5–52:2009 Table B.52.4 for copper conductor with PVC insulation with a wiring condition of ambient
temperature 30°C in air and an installation method of "B2" (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the standard of
IEC 60364–5–52:2009 for suitable cable sizes.
2
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN 61800–5–1:2007 Table 5. So if phase conductor size is
changed, earthing conductor size should also be changed accordingly.
3
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
4
Available in 2015.
208V Input
Current
Current
Current
(CT/I
)
(VT/I
H
(VT/I
)
at 50°C
at 40°C
L
4.4
3.7
4.8
6.1
4.8
6.6
7.2
6.6
7.8
10.2
7.8
11
11.6
11
12.5
16.3
12.5
17.5
23.2
17.5
25
29
25
31
44.2
31
48
56
48
61
64.6
61
75
78
75
88
94.3
88
114
129
114
143
157
143
170
189
170
211
211
261
4
261
312
4
Fuse
Mains and
)
Rating
Motor Cable
L
2
(gG/gL)
Cu (mm
)
6
3*1.5+1.5
10
3*1.5+1.5
16
3*1.5+1.5
16
3*1.5+1.5
16
3*1.5+1.5
20
3*4+4
32
3*4+4
32
3*6+6
50
3*16+16
63
3*16+16
80
3*25+16
100
3*35+16
125
3*50+25
160
3*70+35
200
3*95+50
250
3*150+95
4
4
4
4
Instruction Leaflet IL040016EN
Effective March 2014
Terminal Cable Size
Main Terminal
Earth Terminal
2
2
Cu (mm
)
Cu (mm
)
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.2–6 solid or
0.75–6
0.2–4 stranded
0.5–16
4–16
0.5–16
4–16
0.5–16
4–16
16–35
2.5–25
16–35
2.5–25
16–50
6–50
16–50
6–50
16–50
6–50
50–185
10–120
50–185
10–120
50–185
10–120
4
4
4
4
EATON
www.eaton.com
13