Nidec Commander C200 Guide page 7

Masquer les pouces Voir aussi pour Commander C200:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Removing the finger-guard break-outs
A
1
1
B
1
1
1
C
D
3
STEP 6: Wire the drive up
When wiring the drive the power, ground and control connections, they should be tightened to the recommended
torque settings shown in the table below:
Table 6-1 Recommended torque settings
Model size
All
5
6
7
8 and 9
Commander C200/C300 Step By Step Guide
Issue Number: 2
2
A: Size 5 to 9
B: Size 5 only
2
C: Size 6 only
D: Size 7 to 9
Place finger-guard on a flat solid surface and hit relevant
break-outs with hammer as shown (1). For sizes 7 to 9 pliers
2
2
can be used to remove the break-outs, grasp the relevant
break-out with the pliers and twist it as shown (3).
Continue until all required break-outs are removed (2).
Remove any flash / sharp edges once the break-outs
are removed.
2
Finger guard grommets are supplied in the kitbox for size 5
and 6.
2
Terminal description
Control terminals
Relay terminals
Power terminals
Ground terminals
Power and ground terminals
Power and ground terminals
Power and ground terminals
Torque settings
0.2 N m (0.15 lb ft)
0.5 N m (0.37 lb ft)
1.5 N m (1.1 lb ft)
2.0 N m (1.4 lb ft)
6.0 N m (4.4 lb ft)
12 N m (8.85 lb ft)
15 N m (11.1 lb ft)