Electrochemical corrosion of grounding terminals
Ensure that grounding terminals are protected against corrosion i.e. as could be caused
by condensation.
WARNING
The drive must be connected to the system ground of the AC supply. The ground wiring must
conform to local regulations and codes of practice.
The ground loop impedance must conform to the requirements of local safety regulations.
The drive must be grounded by a connection capable of carrying the prospective fault
current until the protective device (fuse, etc.) disconnects the AC supply.
The ground connections must be inspected and tested at appropriate intervals.
WARNING
Table 6-2 Protective ground cable ratings
Input phase conductor size
≤ 10 mm²
> 10 mm² and ≤ 16 mm²
> 16 mm² and ≤ 35 mm²
> 35 mm²
Control connections
The control terminals are configured by default for the arrangement shown below:
Figure 6-5 Commander C200/C300 control terminal connections
Zero frequency
Drive enable**
Run forward
Run reverse
Analog input 1/
Analog input 2 select
Drive ok
* 250 Vac maximum (UL class1)
** Commander C300 uses 'Safe Torque Off' so terminal 11 is unassigned on the Commander C300. When using a
Commander C300 refer to the 'Safe Torque Off' wiring instructions above.
After completing step 6 re-fit the terminal cover (refer to step 5).
12
Either 10 mm² or two conductors of the same cross-sectional area as the
input phase conductor
The same cross-sectional area as the input phase conductor
16 mm²
Half of the cross-sectional area of the input phase conductor
Digital I/O
24 V user
9
Digital I/O1
10
Digital Input 2
11
Digital input 3
12
Digital input 4
13
Digital input 5
14
Relay 1*
41
42
Minimum ground conductor size
Analog I/O
0V
1
Analog input 1
2
10 V user
4
Analog input 2
5
Analog output 1
7
24 V user
Commander C200/C300 Step By Step Guide
Frequency
10 kΩ
reference 1
Frequency
10 kΩ
reference 2
Frequency output
** C300 only
Safe Torque
Off
ST01
31
0V
STO1
32
0V
STO2
36
ST02
35
Issue Number: 2