Macurco CM-6 Instructions D'utilisation page 20

Masquer les pouces Voir aussi pour CM-6:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5.
Turn on the regulator to start the gas flow and wait with the gas applied continuously.
6.
With the display function turned "On", the CM-6 will show the current concentration of CO or "0" (zero) in clean air. When the
CO concentration reaches the Fan Relay setting (35 ppm, for example) the display will flash back and forth between "FAn" and
"35". With the display function turned "Off", the display does not show the CO concentration, but will show "FAn" as long as the
fan relay is activated.
Note: If the Fan relay does not close within 2 minutes, there are four possibilities:
a.
Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25psi or less.
b.
Unit needs to be re-calibrated (go through recalibration and re-test).
c.
Detector is in need of servicing (return unit to factory for servicing).
d.
Detector has fan relay set to disable (diS) or 100ppm. Set fan relay to 25ppm and repeat the test.
7.
Remove the gas from the sensor. Proceed to Test the Alarm relay or replace the top cover.
Testing the Alarm Relay
Note: The CO concentration to activate the Alarm relay depends on the setting.
1.
Connect the 200ppm cylinder of carbon monoxide to the regulator.
2.
Check the pressure gauge. If there is 25psi or less the cylinder should be replaced.
3.
Place the Test Hood over the CO sensor. Turn on the regulator to start the gas flow.
4.
The Fan relay should activate according to the settings.
20

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cm6-fck

Table des Matières