Control Switch Operation - Franklin Electric SubDrive Solar Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

RUN

2 Control Switch Operation

The SubDrive Solar is designed to utilize up to two control switches for operation. When both
switches are installed, the controller starts to pump and waits to shut off until both switches
read "OPEN". Once it shuts off, the controller then waits to run again until both switches read
"CLOSED". An example application (Figure 10) is to use separate level switches to indicate high
and low water levels. Two pressure switches, one with a high pressure cut-out in the "STOP" input
terminal, and a second low pressure cut-in switch in the "RUN" input terminal can also be used
to manage the system in applications that do not have an open discharge. Parameter 1 should be
changed to "2" in the menu controls. SEE USER DEFINABLE PARAMETERS in operation section of
manual for instructions.
1 Control Switch Operation
Alternatively, the SubDrive Solar controller may be configured to control water level by using
a single input switch. Once properly configured for a single active input with a control switch
installed, the controller starts to pump and waits to shut off until the active switch reads "OPEN".
Once it shuts off, the controller then waits to run again until the switch reads "CLOSED". An
example application (Figure 10) would be to use a single-contact level-switch that keeps the
storage tank as full as possible without overflowing. A single pump control pressure switch can be
used to control the pressure range between an adjustable range (i.e. 30/50 psi pressure switch).
For single level switch control, use only the "RUN" terminal connections. Parameter 1 should be
changed to "1" in the menu controls. SEE USER DEFINABLE PARAMETERS in operation section of
manual for instructions.
0 Control Switch Operation
Lastly, the SubDrive Solar controller may be configured to not use a control switch. The SubDrive
Solar controller defaults to parameter 1 setting of 0 control switch inputs. In this configuration
the SubDrive Solar will always try to run the motor and pump water as long as there is sufficient
power from the solar array or alternate AC power source.
20
COMM.
COMM.
STATUS
MENU
SELECT
UP
DOWN
225979101,3
-
+
RS-485
225996101,2
Error Codes
E1
E2
E3
E4
E5
E6
Display
Status
Run
Idle
Motor
Under
Locked
External
Open
Short
Mode
Mode
Underloaded
Voltage
Pump
Trip
Circuit
Circuit
WARNING – Operation of this equipment requires
detailed installation and operation instructions provided
Suitable for use on a photovoltaic circuit capable of delivering not more
in the Installation/Operation manual intended for use
Service
than 50 DC amps short circuit current, or on a backup AC generator
with this product. Additional copies of the
capable of delivering not more than 5000 amps symmetrical RMS current.
Installation/Operation manual may be ordered by
See manual for allowed ratings of solar array (DC) and generator (AC).
contacting your local Franklin Electric representative.
Use 90 °C wire rated 600V min for DC and 300V min for AC.
Diagnostic Aid
COM
Tighten terminals to 7 in-lbs.
Tighten terminals to 15 in-lbs.
NC
Tighten terminals to 15 in-lbs.
NO
+
-
L1
L2
BLK
RED
(GND)
(GND)
(GRY)
(BLK)
RUN
STOP
TRIP
MOTOR
SOLAR PRIMARY
BACKUP
DC
AC
Multiple electrical power sources may be connected.
Disconnect all electrical power before servicing.
STOP
Figure 9: Control Switch
E7
E8
E9
Overheated
Internal
Controller
Reserved
Error
YEL
(BRN) (GND)
Wiring Connection

Publicité

Table des Matières
loading

Table des Matières