DC Wiring Connections

1. Make sure that the external disconnect switch is off.
2. Make sure that AC power is disconnected (if installed).
3. Make sure that all wires are properly identified and marked:
• the cable from the PV to the external DC disconnect switch;
• the cable from the external DC disconnect to the SubDrive Solar controller.
4. Connect the cables from the external DC disconnect to the terminal block labeled "Solar
Primary DC" and marked +, - and GND. (Figure 5) (Torque specification: 15 in-lbs/ 1.7 N-m).
+
-
SOLAR PRIMARY
DC
CAUTION
Only connect a photovoltaic solar array to the DC input of the SubDrive Solar controller. This
controller is suitable for use on a PV circuit capable of delivering not more than 50 DC amps short
circuit current.
In this drive, the integral solid state short circuit protection of motor wiring does not provide circuit
protection of wiring for input power. Input wiring protection must be provided in accordance
with all applicable national and local electrical codes. In addition, follow any manufacturer's
recommendations for protection of a photovoltaic (PV) array and protection of a generator, if used.
16
COMM.
COMM.
STATUS
MENU
SELECT
UP
DOWN
225979101,3
-
+
RS-485
225996101,2
Error Codes
E1
E2
E3
E4
E5
E6
E7
E8
E9
Display
Status
Run
Idle
Motor
Under
Locked
External
Open
Short
Overheated
Internal
Mode
Mode
Underloaded
Voltage
Pump
Trip
Circuit
Circuit
Controller
Reserved
Error
WARNING – Operation of this equipment requires
detailed installation and operation instructions provided
Suitable for use on a photovoltaic circuit capable of delivering not more
in the Installation/Operation manual intended for use
than 50 DC amps short circuit current, or on a backup AC generator
Service
with this product. Additional copies of the
capable of delivering not more than 5000 amps symmetrical RMS current.
Installation/Operation manual may be ordered by
See manual for allowed ratings of solar array (DC) and generator (AC).
contacting your local Franklin Electric representative.
Use 90 °C wire rated 600V min for DC and 300V min for AC.
Diagnostic Aid
COM
Tighten terminals to 7 in-lbs.
Tighten terminals to 15 in-lbs.
Tighten terminals to 15 in-lbs.
NC
NO
+
-
L1
L2
BLK
RED
YEL
(GRY)
(BLK)
(BRN) (GND)
(GND)
(GND)
RUN
STOP
TRIP
MOTOR
SOLAR PRIMARY
BACKUP
DC
AC
Multiple electrical power sources may be connected.
Disconnect all electrical power before servicing.
Figure 5: DC Wiring Connection

Publicité

Table des Matières
loading

Table des Matières