Pump/Motor Wiring Connections; Control Switch Wiring Connections (Optional) - Franklin Electric SubDrive Solar Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Pump/Motor Wiring Connections

1. Connect the cables from the Pump/Motor Assembly to the Terminal Block labeled "MOTOR"
and marked BLK, RED, YEL, and GND (Figure 8) (Torque specification: 15 in-lbs/ 1.7 N-m).
2. Motors with international leads use Table 2 for motor lead color information to ensure
correct installation.
US
International
BLK
RED
YEL
(GRY)
(BLK)
(BRN) (GND)
CAUTION
For retrofit application, make sure to check integrity of power and motor leads. This requires
measuring the insulation resistance with the suitable megohmmeter. Reference the Franklin Electric
AIM for correct measures (see Table 4. Motor Specifications, pg. 25)
Control Switch
Wiring Connections (Optional)
The SubDrive Solar controller can be operated with control switches to control the ON/OFF
pumping range. Use a normally closed low-voltage control switch with a contact rating suitable for
instrumentation use (i.e. Max: 24 V 15mA)
1. Connect the cables from the "STOP" control switch to the Terminal Block labeled "STOP".
2. Connect the cables from the "RUN" control switch to the Terminal Block labeled "RUN" (Figure 9).
Black (BLK)
Red (RED)
Gray (GRY)
Black (BLK)
Table 2: US and International Wire Color Chart
COMM.
COMM.
STATUS
MENU
SELECT
UP
DOWN
225979101,3
-
+
RS-485
225996101,2
Error Codes
E1
E2
E3
E4
E5
E6
E7
E8
E9
Display
Run
Idle
Motor
Under
Locked
External
Open
Short
Overheated
Internal
Status
Controller
Reserved
Mode
Mode
Underloaded
Voltage
Pump
Trip
Circuit
Circuit
Error
WARNING – Operation of this equipment requires
detailed installation and operation instructions provided
Suitable for use on a photovoltaic circuit capable of delivering not more
in the Installation/Operation manual intended for use
than 50 DC amps short circuit current, or on a backup AC generator
Service
with this product. Additional copies of the
capable of delivering not more than 5000 amps symmetrical RMS current.
Installation/Operation manual may be ordered by
See manual for allowed ratings of solar array (DC) and generator (AC).
contacting your local Franklin Electric representative.
Use 90 °C wire rated 600V min for DC and 300V min for AC.
Diagnostic Aid
COM
Tighten terminals to 7 in-lbs.
Tighten terminals to 15 in-lbs.
Tighten terminals to 15 in-lbs.
NC
NO
+
-
L1
L2
BLK
RED
YEL
(GRY)
(BLK)
(BRN) (GND)
(GND)
(GND)
RUN
STOP
TRIP
MOTOR
SOLAR PRIMARY
BACKUP
DC
AC
Multiple electrical power sources may be connected.
Disconnect all electrical power before servicing.
Yellow (YEL)
Brown (BRN)
Figure 8: Motor Wiring Connection
Ground (GND)
Ground (GND)
19

Publicité

Table des Matières
loading

Table des Matières