4.5 4.5 Modification of the flow direction
ATTENTION
The product assemblies are leak tested at
works. When modifying the flow direction,
please make sure that the seals are not da-
maged and carry out leak test after modifi-
cation.
4.5.1 "Regumat S-130"
Supply
left
1
– Unscrew connection (1).
– Change supply and return column.
– Retighten connection with a torque of 45 Nm.
4.5.2 "Regumat M3-130"
Supply
left
– Loosen connection (1) and screw (2).
– Remove actuator (3).
Supply
left
7
(top view)
10
right
1
1
right
right
4
5
7
6
– Loosen covers (4) and (5).
– Mount spindle of the mixing valve (6) on the
opposite side.
– Retighten covers with a torque of 45 Nm.
– Mount antirotation device (7) on the opposite
side.
– Set spindle of the mixing valve (6) in such a
way that the nose of the adapter points down-
wards. In this position, the downward outlet is
closed by the spindle of the mixing valve
(bypass completely open, cold).
– Set operating switch (10) to manual operation.
– Place rotation indicator (8) onto the actuator
(3) as illustrated.
– Push handle for manual setting (9) onto the
shaft of the mixing valve.
Attention: The handle can only be engaged easily
in a snap-in position. Do not use excessive force
Turn handle for manual setting to the left until
stop. Arrow of the handle is in the blue zone.
– Place actuator onto the shaft of the mixing
valve.
– Introduce and tighten screw (2) together with
the serrated lock washer with a torque of >
5Nm.
– Set operating switch to automatic operation.