Burner Dimensions; Firing Rate - Riello 40 Bio Instructions Pour Installation, Utilisation Et Entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.4

Burner dimensions

Flange
213
160
190
4.5

Firing rate

The MAXIMUM OUTPUT is chosen from within the diagram area
(Fig. 3).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram.
The burner delivery must be selected within area of the diagrams
(Fig. 3). This area is called firing rate and provides the maximum
delivery of the burner in relation to the pressure in the combustion
chamber.
1.0
0.8
0.6
0.4
0.2
0
8
90
Technical description of the burner
10
12
14
110
130
150
170
Burner
350
=
=
The work point may be found by plotting a vertical line from the
desired delivery and a horizontal line from the pressure in the
combustion chamber. The intersection of these two lines is the
work point which must lie within the firing rates.
The firing rate area values have been obtained
considering a surrounding temperature of 20 °C,
and an atmospheric pressure of 1013 mbar (ap-
WARNING
prox. 0 m above sea level).
D5683
16
18
20
190
210
230
9
GB
118
41
Fuel output - kg/h
Thermal power - kW
295
D5283
Fig. 2
Fig. 3
2903443

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

G20474t514570573747469

Table des Matières