Panel With Branch Circuit Breakers: Feed And Load Wiring - Lutron Softswitch128 Guide D'installation

Masquer les pouces Voir aussi pour Softswitch128:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 61
Wiring
(continued)

Panel with Branch Circuit Breakers: Feed and Load Wiring

(120/277/347 V
Typical switch leg
Switched Hot/Live
#14-#10 AWG
(2.5-4.0 mm
)
2
Load
Load Neutral
#14-#10 AWG
(2.5-4.0 mm
)
2
Wire Sizes
120 V
#4 AWG to 250 KCMIL (MCM) (25-185 mm
277 V
#4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm
347 V
#4 AWG to 250/350 KCMIL (MCM) (25-120/185 mm
R
only)
Bypass jumpers -
do not remove
SH
H
SH
H
SH
H
SH
H
SH
H
Branch circuit
breakers for
temporary
lighting
Main lugs
Neutral bus
XP12-1204ML-20 shown
Wiring Tips
• Wire the switching panel similar
to wiring a lighting distribution
panel:
• Run feed and load wiring. No
other wiring or assembly
required.
The switching panel can provide
temporary lighting:
• Wire all loads.
• Leave the bypass jumpers in
place.
• Use branch circuit breakers at
the distribution panel to switch
lights on and off.
Neutral bus
Feed Wiring
2
)
2
)
2
)
Installation Guide for Switching Panels
11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Softswitch128 xpsGrafik systemsGrafik systems xp

Table des Matières