PRECAUTION
• Do not disassemble the battery charger. There are no user-serviceable parts with
the exception of a user-replaceable fuse at the DC ouput wiring compartment.
• Do not operate the battery charger with damaged or substandard wiring.
• In order to maintain watertightness, it is strictly forbidden to dismantle the
charger and/or to modify the casing and/or wirings in any way.
This charger is suitable for use in marine engine compartments, and near fuel
tanks.
Leave at least 10cm / 3inches clearance around the charger for proper
ventilation.
Install the charger in a vertical position to create an optimal ventilation. Note that
wirings are at the bottom of the charger.
All electrical connections to and from the charger must remain accessible all the
time.
The charger must be correctly and strongly fixed.
This device is not a toy and must be kept out of the reach of children.

Connections

ATTENTION
• To prevent overheating, ensure the correct tightening of the connections.
WARNING
• In order to protect the occupants, the main power supply access must be
attached to a differential circuit breaker (refer with technical specifications).
• For safety reason, the green / yellow wire of the power cord must strictly be
connected to the earth of the installation.
• Each access connected to the battery is protected with a sealed fuse integrated
with the wire. Do not remove or change those fuses.
According to the model, the charger is set to be connected to a monophase
network 230V – 50/60 Hz or 115V - 50/60 Hz (refer with technical specifications).
The installation to which the charger is connected must comply with the
standards currently enforced in the country of use.
European Version: the cable N°1 of power cord must be connected to the LINE or
PHASE, the N°2 to the NEUTRAL.
US Version: The battery charger is supplied with an extension cord. Connect it at the
nearby 120 VAC GFCI (Ground Fault Circuit Interrupt) outlet.
3