Special Applications: Finding Breaks
Set-up:
1
Transmitter
Transmitter
indicator showing
signal in
HIGH mode
1. Ensure the wire is De-energized.
2. Connect the Transmitter with the test leads
to the circuit.
3. HIGH signal mode is automatically
activated when the Transmitter is turned on.
Tracing mode:
Tracing a cable to find
breaks or opens
6
Amprobe
®
| info@amprobe.com | Fluke Corporation, Everett, WA 98203 | Tel: 877-AMPROBE (267-7623)
Set-up:
2
Receiver
1. Turn on the Receiver. Tracing mode is
automatically activated.
1. Start tracing the cable until the
signal stops.
2. Verify the place of the fault:
move the Transmitter to the other
end of the wire and repeat tracing
from the opposite end. If the signal
stops at the exact same location the
fault has been located.
Note:
For best results, ground all
De-energized wires that run in
parallel with the black test lead.