Technical specifications

Output power
Electrical supply network
Rated input voltage
Input voltage range
Frequency
Power factor
Harmonic distortion
Leakage current
Load output
Voltage
Frequency
Harmonic distortion
Overload capacity
Battery
Environment
Operating temperature range
Relative humidity
Storage temperature range
Altitude
Noise level
(1) If the output voltage is 200V - 250V, the output power is 15 kVA / 12 kW.
(2) With one EXB module or more, the standard output power is 20 kVA / 16 kW.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the UPS Config software.
(5) Frequency-converter mode is programmable using the UPS Config software.
MX Frame 15000 RT
(1)
15 kVA
/
(2)
13.5 kW
Single phase 230 V / Three phase 400 V
120 / 156 V to 280 V
50/60 Hz (autoselection)
> 0,99
> 5%
1:1 20 mA max. / 3:1 30 mA max.
Single phase 230 V ±3%
50/60 Hz ±0,5%
1:1 < 10% / 3:1 < 20%
105% continuous, 110% 2min,
125% 1min, > 150% 0.5s
15 x 12V - 5 Ah,
sealed lead acid,
maintenance free
20% to 90% (non-condensing)
0 to 1000 m without derating
< 51 dBA

8. Appendices

MX Frame 20000 RT
(1)
20 kVA
/
(2)
18 kW
(3)
(4)
(5)
15 x 12V - 5 Ah,
Two 15 x 12 V - 5 Ah
sealed lead acid,
strings, sealed lead acid,
maintenance free
0°C to 40°C
-25°C to 40°C
MX EXB
maintenance free
34008486EN/AC - Page 43