Installing several detectors in a network
It is possible to inter-connect up to 40 detectors to make alarm activation possible over the
whole range of smoke detectors of the home.
1. After the detector's mounting base has been nstalled, unfasten the connector block.
2. Then do the wiring as follows:
TG 500A / TG 500B
For a cable of 1.5 mm csa, the distance shall not exceed 400 m.
3. Fasten the connector block back onto the supporting base.
4. Lock the detector on its base.
Connect only detectors of the same model within the network.
To install TG501 detectors in a network, an asymmetric power supply can be used.
A separate cutout should be used for protection in this case.
For energy supply and signal forwarding of the smoke detectors a cable
(NYM-0/3 x 1.5 mm
30
or NYM- 4 x 1.5 mm
2
with earth wire) has to be laid separately.
2
TG 501A