Heat Source Connection; Temperature Sensor - Dimplex SI 90TU Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SI 90TU - SI 130TU
Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing a dual dif-
ferential pressureless manifold.
The frost protection function of the heat pump manager is ac-
tive whenever the heat pump manager and the heat circulating
pumps are ready for operation. The system must be drained if
the heat pump is taken out of service or in the event of a power
failure. If heat pump systems are implemented in buildings
where a power failure cannot be detected (holiday homes etc.),
the heating circuit should be operated with suitable frost pro-
tection.

7.3 Heat source connection

The following procedure must be observed when making the
connection:
Connect the brine pipe to the heat source flow and return of the
heat pump.
The hydraulic integration diagram must be adhered to.
ATTENTION!
The supplied dirt trap must be inserted in the heat source inlet
of the heat pump to protect the evaporator against the ingress
of impurities.
The brine must be produced prior to charging the system. The
brine concentration must be at least 25 %. This guarantees
frost protection up to approx. -14 °C.
Only monoethylene glycol or propylene glycol-based antifreeze
may be used.
The heat source system must be de-aerated and checked for
leaks.
ATTENTION!
The brine must contain at least a 25 % concentration of a
monoethylene glycol or propylene glycol-based antifreeze,
which must be mixed before filling.
NOTE
If necessary, the operating range can be extended to a brine
inlet temperature of -10 °C. In this case, the minimum brine
concentration
must
be
temperature -17 C°).
ATTENTION!
The maximum test pressure in the heating circuit and the
brine circuit is 6.0 bar. This value must not be exceeded.
ATTENTION!
A suitable de-aerator (micro bubble air separator) must be
installed in the heat source circuit by the customer.
www.gdts.one
adjusted
to
30 %.
(Freezing
452237.66.52 · FD 9912

7.4 Temperature sensor

The following temperature sensors are already installed or must
be installed additionally:
Outside temperature sensor (R1) supplied (NTC-2)
Return temperature secondary circuit (R2) installed
(NTC-10)
Return temperature primary circuit (R24) installed (NTC-
10)
Flow temperature secondary circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
-20
-15
Temperature in °C
NTC-2 in k
14.6
11.4
NTC-10 in k
67.7
53.4
15
20
25
30
35
2.9
2.4
2.0
1.7
1.4
14.9
12.1
10.0
8..4
7.0
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve il-
lustrated in Fig. 7.2. The only exception is the outside tempera-
ture sensor included in the scope of supply of the heat pump
(see Fig. 7.3)
70
60
50
40
30
20
10
0
-20
-15
-10
-5
0
5
10
External temperature in [°C]
Fig. 7.2:Sensor characteristic curve NTC-10
20
18
16
14
12
10
8
6
4
2
0
-20
-15
-10
-5
0
5
10
External temperature in [°C]
Fig. 7.3:Sensor characteristic curve NTC-2 according to DIN 44574 Out-
side temperature sensor
English
-10
-5
0
5
8.9
7.1
5.6
4.5
42.3
33.9
27.3
22.1
40
45
50
55
1.1
1.0
0.8
0.7
5.9
5.0
4.2
3.6
15
20
25
30
35
40
45
50
15
20
25
30
35
40
45
50
10
3.7
18.0
60
0.6
3.1
55
60
55
60
EN-7

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Si 130tu

Table des Matières