93014.15.06
Bit 0: Host/Local (R/W)
Bit 1: Run/Stop (R/W)
Bit 2: Load/Unload (R/W)
Bit 3: Operating at Minimum Speed (R)
Bit 4: Operating at Maximum Speed (R)
Bit 5: Stopped in Auto Restart (R)
Register 98: Compressor Type
Register 127 & 128: Day
80447162 Rev B
Figure 132 : Manhattan Variable Speed Controller Register 01-Status/Control
0 = Local
1 = Host
0 = Stop
1 = Run
0 = No Loaded Operation
1 = Loaded Operatoin
0 = Operating above Minimum Speed
1 = Operating at Minimum Speed
0 = Operating below Maximum Speed
1 = Operating at Maximum Speed
0 = Not Stopped in Auto Restart
1 = Stopped in Auto Restart
Figure 133 : Manhattan Variable Speed Controller Register Codes
55 = 5.5 kW
75 = 7.5 kW
80 = 7.5 hp
100 = 10 hp
110 = 11 kW
150 = 15 kW
200 = 20 hp
220 = 22 kW
290 = 30 hp
300 = 30 kW
400 = 40 hp
370 = 37 kW
500 = 50 hp
0 = Sunday
4 = Thursday
1 = Monday
5 = Friday
2 = Tuesday
6 = Saturday
3 = Wednesday
Bit 6: Alarm (R)
0 = No Alarms
1 = Alarms
Bit 7: Warning (R)
0 = No Warnings
1 = Warnings
Bits 8 - 9: Normal/Unload Operate (R)
00 = Unloaded Operation
11 = Normal Operation
Bits 10 – 11: Unused
Bit 12: Fixed/Variable Speed Compressor (R)
0 = Fixed Speed
1 = Variable Speed
Bits 13-15: Unit Type (R): Unused
7 = Daily
8 = Weekdays
9 = Weekends