INSTALLATION MANUAL
Connecting wiring
MUCOR-60-H8T
INDOOR UNIT
S2 S1
400 Vac
50 Hz
Use shielded cable for interconnection
Note: Interconnection terminal S1 can be called P, and S2 as Q.
Wiring diagram of indoor unit:
Centralized control
connection CCM
Remote ON/OFF signal and Alarm
MAIN BOARD
ALARM
ON/OFF
CN10
CN11
400 Vac
50 Hz
Remote
Alarm
signal
ON/OFF
ALARM
ON/OFF
CN10
CN11
MAIN BOARD
CN13
S1 S2
X
Y
E
The terminals that are between dashed
lines is optional its use
The operation of ON/OFF signal is as follows:
- With the unit running if the contact CN10 opens unit stops and remote control is locked,
CP shown in the display.
-With the unit stoped if the contact CN10 opens unit will continue stop and remote control
is locked, CP shown in the display.
The alarm signal provides an output of 230Vac when the unit indicates an error code.
NOTE: Only CP shown in the display if the unit has a digital display.
OUTDOOR UNIT
No use
48