7 Assemble the indoor unit. Two people are needed to
lift and fasten the unit. Insert the suspension bolts into
the holes for attaching the unit. Fasten them with the
washers and nuts provided.
8 Remove the side panel and the grille
Suspension
Suspension arm
bolt
Grille
14
9 Assemble the indoor unit on the suspension bolts
using suitable locking elements. Place the indoor unit
level and check that it is aligned with a spirit level to
avoid any leaks.
Suspension
Fig. 10
l
CEILINg INSTALLATION
Side panel
Fig. 11
Shock-proof shim
Washer
bolt
WARNINg
Ensure that the drain pipe slopes at least 1/100.
Gas side
Liquid side
Drain point
(1-2)/100 slope
Installation
Nut
Protruding
part
Fig. 12
Fig. 13
Fig. 14