330-00701
The lamp is flashing.
The lamp is not dimmable.
The minimal dimming level is
set too low.
The dimming profile is incorrect.
There is a PLC malfunction.
The lamp is not suitable.
The dimmer is defective.
The lamp cannot be switched off.
There is leakage current due to
certain dimmable LED lamps or
dimmable economy lamps with
a low electrical load. Leakage
current can also occur due to
capacitive effects of long cabling.
5. USAGE WARNINGS
- PLC control signals that are sent via the mains can interfere with the operation of the dimmer. (This is not a
defect.)
- The dimmer is never electrically separated from the mains due to the operation of the control. In other words
, all parts remain connected to the power even if the load (e.g., the light) is "off".
- This appliance is not suitable for controlling motors.
6. TECHNICAL DATA
- Input voltage: 230V AC ± 10%, frequency 50 Hz
- Mounting: DIN-rail (1 TE = 17.5 mm width)
- Weight: ± 70 g
- Permissible ambient temperature: see power graph
- For use in an environment with a non-condensing humidity (30% - 70%)
- Own power consumption: ± 0.6 W
- Input impedance:
0-10V: 33 kΩ
1-10 V: 22 kΩ
- Maximum temperature of housing (T c ): 90°C
- Maximum wire diameter per connection terminal: 2.5 mm
- Power supply and load: 2 x 1.5 mm
of 1 x 2.5 mm
2
- Input: 2 x 1.5 mm
2
or 1 x 2.5 mm
2
- Minimum load: 5 W
- Protection: thermal overload protection, short-circuit protection
- Complies with the EN 60669-2-1 standards
- Wiring of analogue control:
- Control circuit and power circuit of the dimmer are galvanically isolated.
- The control inputs of the dimmer comply with the requirements for safety extra low voltage (SELV). If the
control signals originate from appliances that also meet the SELV requirements, no specific requirements in
terms of wire diameter or insulation of the control wires apply. You must keep the control wires separate from
the 230V AC wires (min. 10 mm). In this is not the cases, the SELV guarantees do not apply.
- Protection degree: IP20
- Power graph: power according to ambient temperature.
100 %
95 %
90 %
85 %
80 %
75 %
70 %
65 %
60 %
55 %
50 %
0
10
If modular dimmers are fitted near to one another in the electrical cabinet, you can only connect 80% of the
maximum permissible power. A minimal distance of 20 mm is required in order to utilise the full, maximum power.
Also think about ensuring sufficient ventilation in the electrical cabinet. They are often closed-off cabinets, whereby
the internal temperature can increase and the power graph above is applicable.
7. WARNINGS REGARDING INSTALLATION
The installation of products that will permanently be part of the electrical installation and which include
dangerous voltages, shall be carried out by a qualified installer and in accordance with the applicable
regulations. This user manual must be presented to the user. It should be included in the electrical
installation file and it should be passed on to any new owners. Additional copies are available on the
8
Niko website or via Niko customer services.
8. CE MARKING
This product complies with all of the relevant European guidelines and regulations. For radio equipment
Niko llc declares that the radio equipment in this manual conforms with the 2014/53/EU directive. If
applicable, the full text of the EU Declaration of Conformity can be found on www.niko.eu.
EN
nv Niko sa
Check if the lamp is dimmable.
This is shown on the packaging
by the following symbol:
Lower the minimum dimming
level or use a profile with boost
function (LED 3, LED 4, LED 7
or LED 8).
Choose another profile and ad-
just the minimum dimming level.
Refer to the FAQ on dimming at
www.niko.eu/faq
Replace the lamp if it flashes
during dimming the light up
and down.
Replace the dimmer
Fit another lamp with a higher
minimum electrical load. Or fit a
LED compensator (09-016-10
or 310-0500x) over the lamp,
between the switching wire and
the neutral conductor.
2
2
20
30
40
Ambient temperature (°C)
Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail: support@niko.be — www.niko.eu
9. ENVIRONMENT
Do not dump this product with the unsorted waste. Bring it to a recognised waste collection point.
Together with producers and importers, you have an important role to play in the advancement of
sorting, recycling and reusing discarded electrical and electronic appliances. In order to finance the
waste collection and processing, the government levies a recycling contribution in some cases
(included in the purchase price of this product).
10. NIKO CUSTOMER SERVICES
nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium
www.niko.eu
+32 3 778 90 80 – support@niko.eu
50