Troubleshooting Guide - Protemp PT-80-OFR Manuel De L'utilisateur Et Mode D'emploi

Chaufferette au kérosène
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Problem
Heater fires, but shuts down after a
short period of time.
Heater will not operate, or motor runs
for short time.
Fan does not operate when heater is
plugged in and Operating Switch is in
the "ON" position.
Heater makes grinding noise.
Heater does not turn on and the lamp
is not lit.
Poor combustion and / or soot
production.
© 2019 Pinnacle Climate Technologies, Inc.
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
®

TROUBLESHOOTING GUIDE

Possible Cause
1. Dirty Fuel Filter.
2. Nozzle Dirty.
3. Photocell Dirty.
4. Photocell not installed properly.
5. Photocell Defective .
6. Improper electrical connection
between Circuit Board and Photocell.
7. Cooling Fan is obstructed
8. Improper pressure.
1. No Kerosene/ diesel in fuel tank.
2. Corroded Spark Plug or incorrect plug
gap.
3. Dirty Fuel Filter.
4. Dirty Nozzle.
5. Moisture in Fuel/Fuel Tank.
6. Improper electrical connection
between Transformer and Circuit
Board.
7. Transformer Wires not connected to
Spark Plug.
8. Defective Transformer.
1. Broken electrical connection between
Circuit Board and motor.
2. Not enough amps available to power
heater.
1. Air in fuel pump.
1. Temperature limit sensor has
overheated.
2. No electrical power.
3. Fuse break down.
4. Improper electrical connection
between Temperature Limit Sensor and
Circuit Board.
1. Pump Pressure.
2. Poor fuel quality.
OR WHILE CONNECTED TO A POWER SOURCE
12
Kerosene Radiant Heater User's Manual
Solution
1. Clean/replace Fuel Filter.
2. Clean/replace Nozzle
3. Clean/replace Photocell .
4. Adjust Photocell position.
5. Replace Photocell.
6. Check wiring connections (See Wiring
Diagrams, Page 11).
7. Check to be sure cooling fan is not
obstructed.
8. Adjust pump pressure.
1. Fill tank with fresh Kerosene/ diesel.
2. Clean/replace Spark Plug.
3. Clean/replace Fuel Filter.
4. Clean/replace Nozzle.
5. Rinse out fuel tank with clean fresh
Kerosene/ diesel.
6. Inspect all electrical connections. (See
Wiring Diagrams, Page 11).
7. Re-attach Transformer wires to Spark
Plug.
8. Replace Transformer.
1. Inspect all electrical connections on
Wiring Diagrams (Page 11).
2. Use a new extension cord or try another
electrical socket.
1. Sound will stop after 3 seconds. If
grinding sound continues, add fuel to
tank.
1. Push Operating Switch to "OFF" and
allow heater to cool for 5 minutes. Push
Operating Switch back to "ON".
2. Check power cord and extension cord to
insure of proper connection. Test power
supply.
3. Check/replace Fuse.
4. Inspect all electrical connections. (See
Wiring Diagrams, Page 11).
1. Be sure pump pressure is adjusted
correctly.
2. Be sure Kerosene/ diesel is not old or
contaminated.