Festo ASI-MV-4A-Z Notice page 17

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 27
ASI-M..-...-Z
5.2 Connecting the AS-i bus
Pin assignment of
AS-i interface
5.3 Connecting the operating voltage
Pin assignment of
24 VDC interface
5.4 Connecting the sensors (positive switching, pnp)
Pin assignment of
M12 interface
9801b
Connection must be made via the Festo AS-i
cable socket with a yellow AS-i flat cable
(protected against incorrect polarity by
mechanical coding). Use a power exclusively unit
AS-i +
with reliable isolation (low voltage es per PELV)
(brown)
as per IEC-64 (e.g. Festo AS-i combi-power unit
part no. 18949).
Current consumption approx. 25 mA + current
consumption of sensors (max. 60 mA).
AS-i -
(light blue)
Always supply the valves separately with 24 V
operating voltage. Power supply via the AS-i bus
+24 V
is not possible. Use a power unit with reliable
(brown)
isolation (low voltage es per PELV) as per
IEC-64 (e.g. Festo AS-i combi-power unit part
no. 18949). Connect the power unit to the Festo
24 VDC
AS-i cable socket with a black flat cable.
Current consumption approx. 200 mA per output
(max. 5 W per output).
0 V
(light blue)
Current consumption of sensors
(max. 2 x 30 mA):
see manufacturer specifications.
Pin assignment of sensor connection (pnp):
1 = + 24 V
2 = IN-2
3 = OV
4 = IN-1
5 = Earth/Ground
17