IND. CONT. EQ. – 29TS
0508NH
694 049
Warnung, Warning, Varning
. . . . . . . . . . . . . . . . . . . . . . . . .
de Vor Installations- und Wartungsarbeiten Spannungs-
versorgung ausschalten!
Nur PELV-Netzteile nach IEC/DIN EN 60204-1 oder
Class 2 Circuits verwenden!
en Switch off the power supply before carrying out instal-
lation and maintenance work!
Use only PELV power units as per IEC/DIN EN 60204-1
or Class 2 Circuits!
sv Innan installations- och underhållsarbete påbörjas
ska spänningsmatningen kopplas från!
Använd endast PELV-nätdelar enligt IEC/DIN EN
60204-1 eller Class 2 Circuits!
Industrial Control Equipment
Only for use in Class 2 Circuits
This device is intended to be used with a Class 2 power
source or Class 2 transformer in accordance with UL 1310 or
UL 1585.
As an alternative a LV/C (Limited Voltage/Current) power
source with one of the following properties can be used:
– This device shall be used with a suitable isolating source
such that the maximum open circuit voltage potential
available to the product is not more than 24 Vdc and the
current is limited to a value not exceeding 8 amperes
measured after 1 minute of operation.
– This device shall be used with a suitable isolating source
in conjunction with a fuse in accordance with UL 248. The
fuse shall be rated max. 4 A and be installed in the 24 Vdc
power supply to the device in order to limit the available
current.
Field installed conductors for the device shall be segrega-
ted from field and factory installed conductors and uninsu-
lated live parts of other circuits operating at over 150 V to
ground so that a minimum permanent 2 inch (50.8 mm)
separation is maintained, unless the field wiring conductors
have been provided with recognized insulating material
which has an equal or higher voltage rating than the other
circuit involved.
Protection class: NEMA Type 1, 2, 3R, 4, 4X, 12, 13.
Einbauhinweise / Mechanical connection / Mekaniska anslutningar
Adressierung / Addressing / Adressering
de
AS-i-Adresse (Werkseinstellung)
Adressierbereich
#1a,#1b ... #31a,#31b
Anzahl Adressierzyklen
en
AS-i-Address (Default)
address range
#1a,#1b ... #31a,#31b
numbers of address cycles
sv
AS-i-adress (förinställt)
Adressfält
#1a,#1b ... #31a,#31b
Antal adresscykler
AS-i-Modul
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Funktion
Das AS-i-Modul ASI-4DI3DO-M12X2-5POL-Z dient zum An-
schluss von bis zu 4 Sensoren (z. B. Näherungsschalter, Licht-
schranken) und 3 elektrischen Verbrauchern an das AS-Inter-
face.
2 Anwendung
Das Modul ist nur folgendermaßen zu benutzen:
– im Originalzustand, ohne eigenmächtige Veränderungen,
– in technisch einwandfreiem Zustand.
3 Einbau und Inbetriebnahme
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heisse Oberfläche! Kurzschluss bzw. Überlast kann zu Tem-
peraturen > 100 °C führen.
• Befestigen Sie das Modul nur auf hitzebeständigem
Untergrund!
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Der Einbau und die Inbetriebnahme darf nur gemäß der
Bedienungsanleitung und von qualifiziertem Fachpersonal
erfolgen.
– Eingänge nicht mit externer Versorgungsspannung verbin-
den (galvanisch gekoppelt mit AS-i)!
– Zum Betrieb sind die angegebenen Grenzwerte der techni-
schen Daten einzuhalten.
– Das Modul unterstützt A/B-Betrieb gemäß AS-i-Spezifika-
tion 2.11 oder höher.
4 Technische Daten
Typ
ASI-4DI3DO-M12X2-5POL-Z
AS-i Busspannung
26,5 ... 31,6 V DC
Lastspannung
– allgemein
24 V DC ± 25 %
(siehe Technische Daten elektri-
scher Verbraucher)
– gemäß UL
24 V DC, Class 2
Strom AS-i Bus/AUX
max. 4 A/Pin
AS-i-Profil (IO.ID.ID2)
S-7.A.2
AS-i Gesamtstromaufnahme
max. 250 mA
Digitale Ein-/Ausgänge
4/3, PNP
Eingangsverzögerungszeit
typ. 3 ms
Sensorstrom pro Eingang
– allgemein / gemäß UL
max. 240 mA / max. 200 mA
Sensorstrom pro Modul
– allgemein / gemäß UL
max. 240 mA / max. 200 mA
Ausgangsstrom
– allgemein / gemäß UL
max. 1 A / max. 0,5 A
Parallelschalten
ja
Kurzschlussschutz
ja, thermisch
Autom. Spannungswiederkehr
ja
Zulässige Umgebungstempera-
tur
– Betrieb / Lagerung
-5 °C ... +50 °C / -20 °C ... +70 °C
Gewicht
165 g
Höhe/height/Höjd: ca. 34,5 mm
Ø 4,3 mm
max. 2 ± 0,5 Nm
M12: 0,6 Nm ± 0,1Nm
#0a
KASI-ADR
beliebig
NEBU-M12G5-F-0,2-M12G4
#0a
as desired
#0a
valfritt
ASI-PRG-ADR
de
AS-i module
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Function
The valve switching module serves for connecting up to 4
sensors (e.g. proximity switches, light barriers) and 3 electri-
cal consuming devices to the AS-interface.
2 Application
The module may only be used as follows:
– in its original condition without modifications,
– in technically faultless condition.
3 Installation and commissioning
Warnung
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hot surface! Short circuit or overload can lead to tempera-
tures > 100 °C.
• Fasten the module only on a heat-resistant base!
Hinweis
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting and commissioning must be carried out only in ac-
cordance with the operating instructions and only by quali-
fied personnel trained for this purpose.
– Inputs must not be fed with external supply voltages (elec-
trically coupled to AS-i).
– The specified maximum limit values must be observed
during operation.
– The module supports A/B operation as per AS-i specifica-
tion 2.11 or higher.
4 Technical specifications
Type
ASI-4DI3DO-M12X2-5POL-Z
AS-i bus voltage
26.5 ... 31.6 V DC
Load voltage
– general
24 V DC ± 25 %
(see technical specifications of
electrical consumers)
– as per UL
24 V DC, Class 2
Current AS-i bus/AUX
max. 4 A/Pin
AS-i-profile (IO.ID.ID2)
S-7.A.2
AS-i total current consumption
max. 250 mA
Digital inputs/outputs
4/3, PNP
Input delay time
typ. 3 ms
Sensor current per input
– general / as per UL
max. 240 mA / max. 200 mA
Sensor current per module
– general / as per UL
max. 240 mA / max. 200 mA
Output current
– general / as per UL
max. 1 A / max. 0.5 A
Parallel switching
yes
Short-circuit protection
yes, thermal
Autom. voltage recovery
yes
Permitted ambient temperature
– operation / storage
-5 °C ... +50 °C / -20 °C ... +70 °C
Weight
165 g
Elektrischer Anschluss / Electrical connection / El-anslutningar
AS-i Anschluss (M12)/
AS-i connection (M12)/
AS-i-anslutning (M12):
AS-i In/Out:
Pin 1 = AS-i +
Pin 2 = 0 V*)
Pin 3 = AS-i –
Pin 4 = 24 V DC ±25%*)
Pin 5 = n.c.
*) Power load
LED-Anzeige / LED display / LED-indikering
LED 1: Power AS-i (grün/green/grön)
an/on/till
1
2
AS-Interface-Spannung vorhanden
AS-Interface voltage applied
3
AS-Interface spänning finns
aus/out/från
Keine AS-Interface-Spannung am Bus
4
4
No AS-Interface voltage on bus
Ingen AS-Interface spänning på bussen
LED 2: Fault (rot/red/röd)
aus/out/från
5
5
Kein Kurzschluss/Überlast
No short circuit/overload
Ingen kortslutning/överbelastning
blinkt/flashes/binkar
Kurzschluss/Überlast
Short circuit/overload
Kortslutning/överbelastade
an/on/till
AS-Interface-Adresse nicht eingestellt (gleich Null),
Ausfall der Bus-Kommunikation (Watchdog abgelaufen)
AS-Interface address not set (equals zero),
Failure of bus communication (watchdog expired)
AS-Interface adress ej inställd (lika med noll),
Avbrott på busskommunikationen (watchdog överskriden)
en
AS-i modul
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Funktion
Modulen ventilanslutning är avsedd för anslutning av upp till
4 givare (t.ex.. cylindergivare, fotoceller) och 3 elektriska
förbrukare till AS-Interface.
2 Användning
Modulen får endast användas enligt följande:
– i originalskick, utan egna förändringar,
– i tekniskt felfritt tillstånd.
3 Montering och Idrifttagande
Warning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Varm yta! Kortslutning resp. överbelastning kan leda till
temperaturer > 100 °C.
• Fäst endast modulen på ett värmebeständigt underlag!
Please note
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Montering och idrifttagning får endast utföras av behörig
personal enligt bruksanvisningen.
– Anslut inte ingångarna med extern matningsspänning (gal-
vaniskt kopplad med AS-i)!
– Vid drift ska de gränsvärden som anges under Tekniska
data följas.
– Modulen stöder A/B-drift enligt AS-i-specifikation 2.11
eller högre.
4 Tekniska data
Typ
AS-i busspänning
Matningsspänning
– allmänt
– enligt UL
Ström AS-i-buss/AUX
AS-i-profil (IO.ID.ID2)
AS-i total strömförbrukning
Digitala in-/utgångar
Ingångsfördröjningstid
Givarström per ingång
– allmänt / enligt UL
Givarström per modul
– allmänt / enligt UL
Utgångsström
– allmänt / enligt UL
Parallellkoppling
Kortslutningsskydd
Autom. spänningstillkoppling
Tillåten omgivningstemperatur
– Drift / Förvaring
Vikt
Anschluss Funktionserde (FE)
Functional earth connection (FE)
Funktionsjordanslutning (FE)
AS-i In
AS-i Out
4 DI
(Inputs, M12)
3 DO
(Outputs, M12)
LED 3: Aux (grün/green/grön)
an/on/till
aus/out/från
LED 4: Status Eingänge (grün/green/grön)/
LED 5: Status Ausgänge (gelb/yellow/gul)
an/on/till
aus/out/från
sv
Varning
Notera
ASI-4DI3DO-M12X2-5POL-Z
26,5 ... 31,6 V DC
24 V DC ± 25 %
(se tekniska data för elektriska
förbrukare)
24 V DC, Class 2
max. 4 A/Pin
S-7.A.2
max. 250 mA
4/3, PNP
typ. 3 ms
max. 240 mA / max. 200 mA
max. 240 mA / max. 200 mA
max. 1 A / max. 0,5 A
ja
ja, termiskt
ja
-5 °C ... +50 °C / -20 °C ... +70 °C
165 g
Eingänge / Inputs / Ingångar:
0, 1: Pin 1 = +24 VDC
2, 3: Pin 1 = +24 VDC
Pin 2 = Ix+1
Pin 2 = Ix+3
Pin 3 = 0 V
Pin 3 = 0 V
Pin 4 = Ix+0
Pin 4 = Ix+2
Pin 5 = FE
Pin 5 = FE
Ausgänge / Outputs / Utgångar:
0, 1: Pin 1 = n.c.
2:
Pin 1 = n.c.
Pin 2 = Ox+1
Pin 2 = n.c.
Pin 3 = 0 V
Pin 3 = 0 V
Pin 4 = Ox
Pin 4 = Ox+2
Pin 5 = FE
Pin 5 = FE
Lastspannung vorhanden
Auxiliary voltage applied
Matningsspänning finns
Lastspannung fehlt
Auxiliary voltage not applied
Matningsspänning fattas
1-Signal an Ein-/Ausgang
1-signal at input/output
1-signal på in-/utgång
0-Signal an Ein-/Ausgang
0-signal at input/output
0-signal på in-/utgång