PROgRAM: SET
The following menu items are displayed and can be changed:
T1 EIn /
T1 On
T1 Hysterese /
REL T1 delay
The parameters have the following meaning:
T1 On
The switch-on temperature defi nes the switching temperature of the relay T1.
Setting range:
Factory settings:
T1 Hysterese
The hysteresis prevents frequent switching on or off of the relay t1 if the measured
temperature at the inside sensor t1 is equal or frequently in the same range of
the set target temperature T1 EIN (on).
Setting range:
Factory settings:
REL T1 delay
The of ReL t1 delay shows the set the switch-on delay for the relay T1. This
setting prevents frequent switching on or off of the relay T1 by slightly fl uctuating
temperatures or if setpoints T1 EIN (on) or T1 hysteresis have almost the same
values.
Setting range:
Factory settings:
Behavior of relay T1
Abbreviations:
T1
T2
T1 EIn /
T1 On
T1 Hysterese
T1 hysteresis
-40°C bis +120°C
23°C
1 bis 5°C
1°C
0 bis 60 Sek
0 Sek
measured temperature at the indoor sensor
measured temperature at the outdoor sensor
setpoint for the switch-on temperature
setpoint for the hysteresis
Professional humidity switch PLS1000 | 67
Professional humidity switch PLS1000
| 69