F1 (min)
The minimum allowed value for the relative internal humidity. The control is
switched off when the internal humidity has fallen below this value. This can
prevent unwanted dehydration.
Setting range: 0.1% RH ... 100% RH
Factory setting: 20% RH
REL T1 delay
By entering a value to ReL t1 delay, the switch-on delay for the relay t1 is
defi ned. This setting prevents frequent switching of the relay t1, with rapidly
changing dew-point temperatures tP1 or tP2, relatively small dew-point
differences, or with rapidly changing temperatures.
Setting range: 0 to 60 sec
Factory setting: 0 sec
PARAMETER OvERvIEw OF RELAy T1
Abbreviations:
T1
TP1
TP2
dTP
TP_diff_On setpoint for the difference tP1 - tP2 (switch on)
TP_diff_Off setpoint for the difference tP1 - tP2 (switch off)
T1 (min)
T1 (max)
F1 (min)
nOTE: If a sensor is faulty or not connected, the relays will be turned off.
60 |
60 |
58 | Modes/ program/functions
measured temperature at internal sensor (sensor 1)
calculated dew point temperature at internal sensor (sensor 2)
calculated dew point temperature at outdoor sensor (sensor 2)
calculated difference tP1 - tP2
setpoint for the minimum allowed internal temperature
setpoint for the maximum allowed internal temperature
setpoint for the minimum allowed relative humidity (interior)