Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 23
OPTICAL EDGE INSTALLATION
The EASY-LUX main control unit is configured for the installation
of one 24 Vdc powered optical edge and transmitter power
regulation.
Connect the transmitter and receiver in accordance
with the following table.
TRANSMITTER
L6
L8
BLUE CABLE
L9
BLACK CABLE
L10
L11
BROWN CABLE
After having made the connections, power-up the main control
unit and adjust the power using the trimmer TR1 located on the
control unit so as to obtain optimal edge operation.
FIRE / ALLARM INPUT
Safety input for connecting a fire or other type of alarm requiring
the immediate automatic opening of the door.
The FIRE command should be connected between the FIRE (L7)
and COMMON (L8) terminals.
When the FIRE contact is opened, the door is opened and cannot
be closed again until the contact is reset.
NOTE: If the input is set as an alarm (
contact is open, the port cannot be opened. If the port is already
open, it is closed.

PLUG IN RECEIVER

The control unit is suitable for plugging in a MR receiver.
MR module receiver is provided with 4 channels and each of
them is suitable for a command of the control unit:
g
• CHANNEL 1
START/UP
g
• CHANNEL 2
STOP
g
• CHANNEL 3
DOWN
g
• CHANNEL 4
COURTESY LIGHT
m
WARNING: Before programming 4 channels and
function logics read carefully the instructions of MR
RECEIVER
BLACK CABLE
BLUE CABLE
BROWN CABLE
in4
oFF
=
), when the FIRE
OPERATION WITH A TIMER
The control unit allows the connection of a timer for
programming door opening and closing times.
To use this function, it is necessary to set the Lo 3 function (see
FUNCTION TABLE) on the AUTOMATIC LOGIC (on) and the
function on the TIMER (
The timer should be connected between the START (L1) and
COMMON (L3) terminals.
Each time the timer closes the contact, the automation device
opens the door and remains paused until the contract is released.
At this point the countdown starts, for the length of the pause
time set, after which the automation device closes the door.
FUNCTIONING WITH KEYPAD
The keypad buttons operate in parallel with the terminal controls.
These all remain active, including the STOP command, and must
be jumpered to ground if not used.
Versions supplied with keypads also allow the automation
device to operate in DEAD MAN mode should the safety devices
malfunction.
By pressing and holding the button on the keypad, the
automation device is activated after 5 seconds, overriding the
safety devices; the motor stops immediately as soon as the
button is released.
NOTE: This function is also available from the terminal
Lo 5
board if the
function is set to EMERGENCY
- 14 -
oFF
)
Lo 5

Publicité

Table des Matières
loading

Table des Matières